Installation:
The L10 UltraBlade Pro Dynamic Red is a recessed ceiling mount fitting. The UltraBlade Pro Dynamic Red
can be attached directly to any solid surface, or to a ceiling tile. The Fitting comes with an attached Flex
and Plug. Please follow the steps below to install the Exit:
•
Create a cut-out (350mm x 70mm) in the mounting surface.
•
Remove the Fire Panel Input terminal block by disengaging the clip. Refer to Image below.
•
Route the power cord to the mains connection and connect the 240VAC supply.
•
Route 24/VF control cables through the access hole and connect to the terminal block as per next
step.
•
Connect positive signal of RED activation to I
•
Connect positive signal of GREEN activation to I
•
Reinstall the terminal block.
•
Insert the Fitting into the ceiling cavity tighten the (4) clamping screws.
•
Alternately, fix the Fitting to a solid surface using (4) screws through the surface material.
•
Install the cover plate, Apply power to the fitting and test.
•
To disable the Dynamic Green mode coming on in Emergency mode Set dipswitch 1 to OFF
position.
NOTE: For the Dip Switch setting to take effect the power and battery will need to be
disconnected and reconnected.
Dynamic Red 24 Volt (24V)/Volt Free (VF) Operation and Testing
Activation of the Dynamic Red/Green is controlled via 24V/VF control interface. The fitting comes pre-set
as normally OFF. This is switched via an intelligent circuit inside the fitting. This is controlled by the
24V/VF input from a fire panel or other source. If you would like to change the activation of the Dynamic
Red/Green from Normally OFF to Normally ON change the Dip Switch no.2 (RED)/ no.3 (GREEN) found
next to the fire Panel Input terminal block
2
and negative signal to C (Common).
1
and negative signal to C (Common).
Selecting the Type of the Interface
The fitting comes pre-set to the Volt Free(VF) control interface, to change this to 24V you will have to
change the switch from VF to 24V found next to Fire Panel Input Terminal Block. Please see image
below.
Zoneworks, HIVE (HV/HVG) and DATA Monitored Options
Luminaires with part numbers having
-ZW, -HV, -HVG, -DATA
modules (nodes). These fittings are monitored using either Powerline Carrier Technology that utilises the
power cable to provide data communication or a dedicated data cable to/from data routers installed on a
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre).
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each
fitting and can be commissioned by scanning of the supplied barcode. The LED Test Switch indicator
provides a multifunction indication of the status of the luminaire during testing and normal operation:
Option
State
ZW, HV, HVG,
Commissioned
DATA
ZW, DATA
Un-commissioned
Un-commissioned
HV, HVG
With network connectivity
Un-commissioned
HV, HVG
Without network connectivity
ZW, DATA
Emergency Light Test In Progress
HV, HVG
Emergency Light Test In Progress
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or "cycled". The Li-ion battery in this fitting has been selected to give excellent long life
performance in a controlled AS/NZS 60598.2.22 testing environment. Excessive battery cycling will
reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a
result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
are fitted with Zoneworks communications
LED Operation
LED on Solid (Green)
Batt plugged-in: Amber 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: Amber 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: Amber 250mS, green
250mS,Amber 250mS, green 250mS,
green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
LED flashes at Amber 5s ,0ff 1s
LED flashes at Amber 1s , 0ff 1s
1942417
V1.5
16 February 2023
Need help?