Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
For the first test, the emergency lamp must remain illuminated for at least 2 hours (4hrs for -4HR
fittings) after disconnection from the mains supply.
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to
remain illuminated for the requisite time, remedial action must be taken to repair the situation and
once completed, the unit must pass a subsequent test. For more specific information, please refer to
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards.
Press and hold Test Button, the product will go into Dynamic Red mode for the initial 60 seconds of
the test button being pressed and then switch to Dynamic Green.
NOTE: Initiating a Function or Duration test using the Zoneworks Software will trigger the Dynamic Red
Mode for 60 seconds then Dynamic Green for completion of the test.
Networking:
When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert the
relevant Smart Node PCA.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check:
A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check:
A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Fault:
The Dynamic Green is not sequencing.
Check:
The 24 Volt/VF control is connected and turned on.
Polarity of 24V control.
Check that the correct interface control is selected.
Fault:
The Dynamic Red is not illuminated.
Check:
The 24 Volt/VF control is connected and turned on.
Polarity of 24V control.
Check that the correct interface control is selected.
Check that the Dynamic Red is activated on the dip switches.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
Please refer to the technical label on the product for classification.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz
L10™ UltraBlade Pro Dynamic Red
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the requirements of
AS2293.3:2005(when not activated in the dynamic green or red
cross mode) and AS/NZS CISPR22: 2009
Note: AS2293.3 Compliance not applicable to -RU and -RD
Products
Models:
DYRL-xUP-uu-vv-ww-xx-yy-zz
Testing:
Zoneworks
xx = ZW
Z/W DATA
xx = DATA
Zoneworks HIVE
xx = HV/HVG
xx=NO
Normally Open
Normally Closed
xx=NC
Activated Only by Fire
xx=AOFP
Panel
Weatherproof
x=W
Spare Parts:
1530050
Replacement Battery (Extra for -4HR)
1530250
Replacement Battery
AUM01570070001
Replacement Emergency Driver
AUM01970160001
Replacement Emergency Driver (-HVG)
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, ensure
that the electricity supply has been switched off and isolated. Installation must be carried out in accordance with
the relevant Australian and International Standards.
Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not
purport to recommend its products for use in any particular application or to achieve any particular outcome.
Purchasers and users of its products must take their own steps to ensure compliance with statutory
requirements, safe practice and suitable application of the products
Victoria (Head Office &
Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
New Zealand
Phone: +64 800 548 448
Options:
Running man
yy=R
Running man with right arrow
yy=RR
Running man with left arrow
yy=RL
Running man with Up arrow
yy=RU
Running man with down arrow
yy=RD
Dynamic Green Disabled
uu=DDG
Theater Mask
vv=TH
SoundEscape module
ww=SND
4 Hour run time
zz = 4HR
1942417
V1.5
16 February 2023

Advertisement

loading
Need help?

Need help?

Do you have a question about the CleverEVAC L10 UltraBlade Pro Dynamic Red and is the answer not in the manual?

Questions and answers

Summary of Contents for Clevertronics CleverEVAC L10 UltraBlade Pro Dynamic Red

  • Page 1 Please refer to the technical label on the product for classification. the relevant Australian and International Standards. Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not Warranty: purport to recommend its products for use in any particular application or to achieve any particular outcome.
  • Page 2 AS/NZS 60598.2.22 testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 1942417 V1.5...