Putting Into Operation; Safety; Earthing Of The Instrument; Connection To The Faulty Cable - Megger SWG 500 Operating Manual

Shock discharge generator
Table of Contents

Advertisement

2

Putting into operation

2.1

Safety

The shock discharge generator SWG 500 releases dangerous
contact voltages. Hence the instrument must be operated by
specialists or personnel who have been trained or instructed in
the use of the instrument. The following safety precautions
should be adhered to:
Para. 2.2.
Para. 2.3.
Para. 2.4.
Para. 2.5.
Para. 2.6.
2.2

Earthing of the instrument

Prior to putting into operation, the Instrument has to be
earthed. For this purpose, the earthing terminal (13) is to be
connected to a reliable protective earth by means of the
earthing lead supplied. The protective earthing provided
through the earthing contact of the mains supply lead is not
sufficient.
2.3

Connection to the faulty cable

The plug of the high voltage lead is connected to the high
voltage socket (15) and is secured by means of the fixing
screw. Now a micro contact inside the instrument closes and
renders the instrument ready for the connection of a mains
supply.
Earthing of the instrument
Connection to the faulty cable
Isolation of open cable ends
Selection of a suitable surge voltage
Safety terms
3

Advertisement

Table of Contents
loading

Table of Contents