VRF SYSTEM
INDOOR UNIT

Duct Type

INSTALLATION MANUAL

For authorized service personnel only.
Contents
1. SAFETY PRECAUTIONS ............................................. 2
2.2. Special tool for R410A ........................................... 2
2.3. Accessories ........................................................... 3
3.1. Selecting an installation location ........................... 3
3.2. Installation dimension ............................................ 4
3.3. Installation the unit................................................. 4
4.1. Selecting the pipe material .................................... 5
4.2. Pipe requirement ................................................... 6
4.3. Flare connection (pipe connection) ....................... 6
4.4. Installing heat insulation ........................................ 7
5. INSTALLING DRAIN PIPES ......................................... 7
6.1. Electrical requirement ............................................ 9
6.2. Wiring method ....................................................... 9
6.3. Unit wiring .............................................................. 9
6.4. Connection of wiring ........................................... 11
7.1. Setting the address.............................................. 11
7.2. Custom code setting ............................................ 12
7.3. Function setting ................................................... 12
9. CHECK LIST ............................................................... 13
10. ERROR CODES ......................................................... 13
PART NO. 9373870036-02

Advertisement

Chapters

Table of Contents
loading

Summary of Contents for Fujitsu ARXC36L

  • Page 1: Table Of Contents

    VRF SYSTEM INDOOR UNIT Duct Type INSTALLATION MANUAL For authorized service personnel only. Contents 1. SAFETY PRECAUTIONS ..........2 6. ELECTRICAL WIRING 6.1. Electrical requirement ..........9 2. ABOUT THE UNIT 6.2. Wiring method ............9 2.1. Precautions for using R410A refrigerant ....2 6.3.
  • Page 2: Safety Precautions

    1. SAFETY PRECAUTIONS 2.2. Special tool for R410A • Be sure to read this Manual thoroughly before installation. WARNING • The warnings and precautions indicated in this Manual • To install a unit that uses R410A refrigerant, use dedicated contain important information pertaining to your safety. Be tools and piping materials that have been manufactured sure to observe them.
  • Page 3: Accessories

    Name and Shape Q’ty Application 2.3. Accessories Drain hose For installing drain pipe WARNING • For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious Hose Band For installing drain accidents such as the unit falling, water leakage, electric hose...
  • Page 4: Installation Dimension

    • Install the indoor unit, outdoor unit, power supply cable, 3.3. Installation the unit transmission cable, and remote control cable at least 1 m away from a television or radio receivers. The purpose of WARNING this is to prevent TV reception interference or radio noise. • Install the air conditioner in a location which can (Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
  • Page 5: Pipe Installation

    • Thicknesses of copper pipes used with R410A are as shown in the table. • The static pressure outside the unit is as follows. • Never use copper pipes thinner than those indicated in the ARXC36L Model: 100-200 Pa table even if they are available on the market. ARXC45/60L Models: 100-250 Pa • If an intake duct is installed, take care not to damage the Thicknesses of Annealed Copper Pipes (R410A) temperature sensor (the temperature sensor is attached to the intake port flange).
  • Page 6: Pipe Requirement

    Width across Pipe outside Width across flats 4.2. Pipe requirement flats diameter [mm (in.)] of Flare nut [mm] 6.35 (1/4) CAUTION 9.52 (3/8) • Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for 12.70 (1/2) difference of its elevation.
  • Page 7: Installing Heat Insulation

    INSTALL THE DRAIN HOSE TO THE MAIN AND Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)] SAFETY DRAIN PORT 6.35 (1/4) dia. 16 to 18 (160 to 180) Working procedure 9.52 (3/8) dia. 32 to 42 (320 to 420) (1) Install the attached drain hose to the main and safety 12.70 (1/2) dia.
  • Page 8: Electrical Wiring

    6. ELECTRICAL WIRING WARNING • Electrical work must be performed in accordance with this NO GOOD Manual by a person certified under the national or regional regulations. Be sure to use a dedicated circuit for the unit. An insufficient power supply circuit or improperly INSTALL THE DRAIN PIPE performed electrical work can cause serious accidents 1 Main drain such as electric shock or fire. On the main drain, provide one trap near the indoor unit.
  • Page 9: Electrical Requirement

    CAUTION 6.2. Wiring method • Ground the unit. Do not connect the ground cable to a gas pipe, water (EXAMPLE) pipe, lightning rod, or a telephone ground cable. Improper grounding may cause electric shock. POWER SUPPLY BREAKER OUTDOOR UNIT • Do not connect power supply cables to the transmission TRANSMISSION or remote control terminals, as this will damage the product.
  • Page 10 WARNING • Use ring terminals and tighten the terminal screws to the specified torques, otherwise, abnormal overheating may be produced and possibly cause heavy damage inside the unit. Loop Tightening torque M4 screw 1.2 to 1.8 N·m Screw with (Power supply/L, N, GND) (12 to 18 kgf·cm) Screw with special washer special 6.3.2. Transmission and Remote control cable washer Cable end (Loop) Cable...
  • Page 11: Connection Of Wiring

    7. FIELD SETTING CAUTION • To peel the film from the lead cable, use a dedicated tool • Refer to the following three items for setting the FIELD that will not damage the conductor cable. SETTING address. The respective settings are included below. • When installing a screw on the terminal block, do not cut (1) IU AD, REF AD SW settings ... This section the cable by overtightening the screw. On the other hand, (2) Remote control settings ..Refer to the wired or an undertightened screw can cause faulty contact, which wireless remote control will lead to a communication failure.
  • Page 12: Custom Code Setting

    (1) Indoor unit address 7.2. Custom code setting Rotary switch (IU AD × 1)..Factory setting “0” Rotary switch (IU AD × 10)..Factory setting “0” Selecting the custom code prevents the indoor unit mix-up. When connecting multiple indoor units to one refrigerant (Fig. B) system, set the address at IU AD SW as shown in the (Up to 4 codes can be set.) Table A. Perform the setting for both the indoor unit and the remote controller.
  • Page 13: Test Operation

    ○ 9. CHECK LIST Enable Disable Pay special attention to the check items below when Filter Enable or disable the filter installing the indoor unit(s). After installation is complete, be indicator Display indicator. Setting 02 is for use sure to check the following check items again. action only on with a central remote control.
  • Page 14: Error Codes

    10. ERROR CODES If you use a wired type remote control, error codes will appear on the remote control display. If you use a wireless remote control, the lamp on the photodetector unit will output error codes by way of blinking patterns. See the lamp blinking patterns and error codes in the table below.
  • Page 15 VRF 系统 室内机组 风管式 安装说明书 只供授权专业维修人员使用。 目录 6. 电气接线 1. 安全注意事项 ..............2 6.1. 电气要求 .................9 2. 关于机组 6.2. 接线方法 .................9 2.1. 使用 R410A 制冷剂时的注意事项 ........2 6.3. 机组连线 .................9 2.2. R410A 的专用工具 ............2 6.4. 线路的连接 ..............10 2.3. 附件 .................3 7.
  • Page 16: 安全注意事项

    1. 安全注意事项 2.2. R410A 的专用工具 • 安装之前务必彻底阅读该说明书。 警告 • 该说明书指出的警告和注意事项包含与您的安全密切相关的 • 要安装使用 R410A 制冷剂的机组,请使用专供 R410A 使 重要信息。请务必遵循这些信息。 用而制造的专用工具和管道材料。由于 R410A 制冷剂的压 • 将该说明书与操作手册交给用户。请用户将它们收藏好,以 力约是 R22 的 1.6 倍,未使用专用的管道材料或不当的安 便日后使用,例如更换机组位置或对机组进行修理。 装可能会导致管道破裂或造成人身伤害。另外,还可能会 该标志表示如果步骤执行失当,可能会导 导致如漏水、电击或火灾等严重事故。 警告 致用户死亡或严重伤害。 • 请您的经销商或专业安装人员依照该安装说明书安装机组。 工具名称 变更内容 机组安装不适当可能造成严重的事故,例如漏水、电击或 压力较高,不能使用传统的压力计 火灾。如果没有依照安装说明书中的说明来安装室内机组, 测量。为了避免与其它制冷剂错误...
  • Page 17: 附件

    2.3. 附件 3. 安装工作 对于分体式空调,安装地点尤为重要,因为首次安装后,移动 警告 位置非常困难。 • 安装时,请务必使用制造商供应的部件或其他规定部件。 使用非规定部件可能造成严重的事故,例如机组掉落、漏 3.1. 选择安装位置 水、电击或火灾。 请按照以下要求与用户一起决定安装位置。 • 本机配有以下安装部件。请按照需要使用。 • 请妥善保管安装说明书,并且不要在安装工作完成前丢弃任 何其它附件。 警告 • 选择能有效支撑室内机重量的安装位置。将机组安装牢固, 说明 数量 应用 以免倾倒或坠落。 使用说明书 注意 请勿将机组安装在下列区域 : • 盐含量高的区域,例如海边。这会损坏金属部件,使部件 掉落或使机组漏水。 (本书) 安装说明书 • 充满矿物油或包含大量溅油或蒸气的区域,例如厨房。这 会损坏塑料部件,使部件掉落或使机组漏水。 • 会产生对设备有负面影响的物质(例如硫磺气体、氯气、 酸或碱)的区域。这会腐蚀铜管和铜焊接合,从而造成制...
  • Page 18: 安装尺寸

    3.3.1. 安装吊具 3.2. 安装尺寸 距天花板至少 20 mm 处安装。 悬吊螺栓安装示意图。 1,050 mm 85 mm 400 mm 1,000 mm 155 mm 气流 气流 气流 1,080 mm 提供用于检查的检修孔,如下图所示。 切勿在维修空间布置线路或照明设施,否则会妨碍维修。 专用螺母 A(大) 悬吊螺栓 M10 (附件) (现场供应) 气流 垫圈 (现场供应) 机组 吊具 气流 500 mm 或以上 30 mm 或以上...
  • Page 19: 管道安装

    残油量最好小于 40 mg/10 m。 注意 • 使用的铜管不能带有压扁、变形或变色的部分(尤其是在 • 为了防止别人触碰机组内部的部件,请务必在进气口和出 内部表面) 。 否则,膨胀阀或毛细管可能会被污染物堵塞。 气口安装格栅。格栅必须设计为无法用工具拆卸。 • 管道选择不当会降低性能。 由于使用 R410A 的空调会比 • 机组外静压如下 : ARXC36L 机型 : 100-200 Pa 使用传统的制冷剂时承受更高的压力,因此需要选择适当 ARXC45/60L 机型 : 100-250 Pa 的材料。 • 如果安装了进气管,请小心不要损坏温度传感器(温度传 • 使用 R410A 的铜管厚度如表所示。 • 绝对不要使用厚度不足于表中所示的铜管,即使市场上有售。 感器安装在进气口法兰上) 。...
  • Page 20: 管道要求

    4.2. 管道要求 扳手开口宽度 扩口螺母的扳手开口 管道外径 [mm (in.)] 宽度 [mm] 注意 6.35 (1/4) • 有关连接管道长度或不同标高的规格,请参见室外机的安 9.52 (3/8) 装说明书。 12.70 (1/2) 15.88 (5/8) • 使用带防水热绝缘材料的管道。 19.05 (3/4) 注意 4.3.2. 弯管加工 • 请在气体和液体管道周围安装绝热材料。否则可能会导致 • 用手或弯管器使管道成形。注意请勿将它们压扁。 漏水。 • 弯曲管道时角度不应超过90˚。 请使用抗热能力超过 120℃的绝热材料。 (仅限逆循环型) • 如果反复弯曲或拉伸管道,材料将变硬,以至很难再次弯曲 此外,如果安装制冷剂管道的地方的湿度可能会超过...
  • Page 21: 安装绝热材料

    4.4. 安装绝热材料 确保没有空隙 软管卡子(附件) 请在完成制冷剂泄漏检查后安装管接头绝热材料(有关详细信 息,请参见室外机的安装说明书) 。 软 PVC 侧 排水盘 接管绝热材料 将该部分用绝热材料包 (附件) 住。 排水软管 10~15 mm (附件) 胶粘剂 涂刷 接管 硬 PVC 侧 区域 (现场供应) 扎线带(大) 绝热材料 排水管(VP25) (附件) (现场供应) 4mm 或以下 注意 将排水软管绝缘材料缠裹在排水软管连接处的四周。 • 绝热材料与产品之间不得有间隙。 排水软管绝缘材料 (附件) 5.
  • Page 22: 电气接线

    1 主排水口 6. 电气接线 在主排水口上靠近室内机处形成一个存水弯。 机组 警告 H1=100 mm(近似值) H2=50-100 mm • 必须由持有证书的人员根据国家或地方法规并按照本说明 书执行电气作业。务必使用机组专用的电路。电源电路供 主排水管 电不足或不当的电气作业可能会导致如电击或火灾的严重 事故。 • 开始工作前,检查室内机和室外机是否没有通电。 • 使用附带的连接线和电源线,或者制造商指定的线缆。连 接不当、绝缘不充分或者超出了允许的电流限制可能会导 存水弯 致电击或火灾。 • 对于接线,使用指定类型的电线,将其牢固连接,并确保 2 安全排水口 电线的外力没有施加到接线端子上。电线连接或紧固不当 安全排水口不需要有存水弯。如果将安全排水口连接到主排 可能会导致如端子过热、电击或火灾的严重事故。 水口,则应在主存水弯以下连接。 • 请勿改装电源线、使用延长线或者使用接线中的任何支线。 机组 连接不当、绝缘不充分或者超出了允许的电流限制可能会 导致电击或火灾。 • 将接线板号码与室外机上的连接线颜色相匹配。错误的接 主排水管 线可能会导致电气部件烧毁。...
  • Page 23: 电气要求

    • 操作 PCB 时,机身上的静电可能造成控制 PCB 发生故障。 6.3. 机组连线 请遵循下列注意事项 : • 将电线连接到接线板之前。 • 对室内和室外机组以及外围设备使用接地线。 6.3.1. 电源线 • 切断电源(断路器) 。 • 请触摸室内和室外机组金属部分 10 秒以上,以释放机身 静电。 • 请勿触碰接线 PCB 上的部件端子和布线模式。 地线 6.1. 电气要求 电源线 230 V 额定电压 198 - 264 V 操作范围 A.
  • Page 24: 线路的连接

    警告 • 将端子螺钉拧紧到指定的扭矩,否则可能会造成异常过热 环形端子 并可能造成机组内部严重损坏。 套管 拧紧扭矩 M3.5 螺钉 0.8 至 1.0 N · m (传输 /X1, X2) (8 至 10 kgf · cm) (遥控器 /Y1, Y2, Y3) 带特殊垫片的螺钉 带特殊垫片 的螺钉 注意 环形端子 • 要剥去引线上的绝缘层,请使用不会损坏导线的专用工具。 环形 电线 端子 电线 • 在接线盒上安装螺钉时,请勿过度拧紧螺钉而折断电线。 同时,过度拧紧的螺钉可能造成错误接触,从而导致通信...
  • Page 25: 现场设置

    (1) 室内机地址 7. 现场设置 旋转开关 (IU AD × 1)....出厂设置“0” 旋转开关 (IU AD × 10).... 出厂设置“0” • 要设置现场设置地址,请参考下列 3 个项目。以下包括了相 将多台室内机连接到一个制冷剂系统时,请参见表 A 中 IU 应的设置。 AD SW 处的地址。 (1) IU AD, REF AD SW 设置 ..本部分内容 (2) 遥控器设置 ....... 有关详细的设置信息,请参 (2) 制冷剂回路地址...
  • Page 26: 用户代码设置

    7.2. 用户代码设置 7.3. 功能设置 选择用户代码可以防止室内机信号混同。 (图 B) • 可以使用有线或无线遥控器执行功能设置。 (可以设置多达 4 个代码) (遥控器为选购设备) • 有关详细的设置信息,请参阅有线或无线遥控器的说明书。 为室内机和遥控器执行该设置。 (将 IU AD, REF AD SW 设为 0) • 有关室内机地址和制冷剂回路地址设置,请参阅“7.1 设置地 图 B 址” 。 • 开始设置之前,请打开室内机的电源。 混同 代码变化 * 打开电源时,室内机初始化 EEV,所以请确保在打开电源 室内机 之前已执行了管道气密性测试和抽真空作业。 * 打开电源前,请再次检查以确保没有接线错误。...
  • Page 27: 检查项目表

    有线遥控器显示 9. 检查项目表 故障代码 安装室内机(组)时,请特别注意以下的检查项目。安装完成 后,请确保再次检查以下的检查项目。 检查项目 如果未正确执行 检查框 正确地安装了室内机了 振动,噪音,室内机可能 有关指示灯闪烁的详细标记方法,请参阅“IR 接收器”或“遥 吗? 掉落 控器(有线式) ”的安装说明书。 已检查气体泄漏(制冷 无制冷,无制热 剂管道)了吗? 已完成绝热工作了吗? 漏水 室内机组排水容易吗? 漏水 电源电压与室内机标签 不运转,发热或烧坏 上显示的相同吗? 电线和管道全都连接正 不运转,发热或烧坏 确吗? 室内机接地了吗? 短路 连接电缆具有规定的粗 不运转,发热或烧坏 细吗? 保持进口和出口无阻塞 无制冷,无制热 物了吗? 安装完成后,向用户说明 正确的操作和处理了吗? 10.