Indoor Unit Error Display; Outdoor Unit Display - ComfortStar CVH-18-2SH Service Manual

Hide thumbs Also See for CVH-18-2SH:
Table of Contents

Advertisement

7.2 Indoor Unit Error Display

Timer
Operation lamp
lamp
★ 1 time
X
★ 2 times
X
★ 4 times
X
★ 6 times
X
★ 6 times
X
★ 1 time
★ 5 times
X
★ 5 times
X
★ 5 times
X
★ 5 times
X
★ 12 times
X
★ 5 times
X
★ 9 times
X
★ 8 times
X
★ 7 times
★ 2 times
★ 3 times
★4 times
★ 5 times
★ 1 time
★ 7 times

7.3 Outdoor Unit Display

7.3.1 Outdoor Unit Point Check Function
A check switch is included on the outdoor PCB.
Push SW1 to check the unit's status while running. The digital display shows the following codes each
time the SW1 is pushed.
Display
LED STATUS
EH
00/EH
Indoor unit EEPROM parameter error
0A
EL 01
Communication malfunction between indoor and outdoor units
EH 03
Indoor fan speed malfunction
EH 60
Indoor room temperature sensor (T1 ) malfunction
EH 61
Evaporator coil temperature sensor (T2) malfunction
PC 08
Current overload protection
EC 53
Outdoor ambient temperature sensor (T4 ) malfunction
EC 52
Condenser coil temperature sensor (T3) malfunction
EC 54
Compressor discharge temperature sensor (T5) malfunction
EC 51
Outdoor unit EEPROM parameter error
EC 07
Outdoor fan speed malfunction
Indoor coil outlet pipe sensor(Located on outdoor unit low pressure
EC 56
valve)
Indoor PCB/Display board communication error
EH 0b
Refrigerant leakage detection
EL 0C
PC 00
Inverter module (IPM) malfunction
PC 01
Over-voltage or under-voltage protection
High temperature protection of compressor top(OLP)/ High
PC 02
temperature protection of IPM board
PC 0L
Low ambient temperature protection
PC 04
Compressor drive malfunction
——
Indoor units mode conflict
PC 03
Low pressure protection
★ flash ,  light, X extinguished
41
ODU
Error
——
E2
——
——
——
——
E4
E4
E4
E0
E8
——
——
——
P6
E5
——
LP
——
——