1. DESCRIPTION
Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH)
Upright Sprinkler VK570 is a thermosensitive glass bulb spray sprinkler with a
14.0 (202 metric
) nominal K-Factor. The sprinkler produces the flows required
*
to meet Ordinary Hazard density requirements at lower pressures than 8.0 or
11.2 (115.2 or 161.4 metric*) K-Factor sprinklers. The glass bulb operating ele-
ment and special deflector characteristics meet the challenges of quick response
extended coverage standards. Viking EC/QREC Ordinary Hazard Sprinklers are
available in various finishes and temperature ratings to meet design requirements.
The Polyester coatings can be used in decorative applications where colors are
desired. In addition, the ENT coating has been investigated for installation in cor-
rosive environments and is listed as indicated in the Approval Charts. The Viking
VK570 Sprinkler may be ordered and/or used as an open sprinkler (glass bulb and
pip-cap assembly removed) on deluge systems. Refer to Ordering Instructions on
the next page.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
NYC Approved: MEA 89-92-E, Volume 38
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2007.
Minimum Operating Pressure: Refer to the Approval Charts.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 3/4" (20 mm) NPT
Nominal K-Factor: 14.0 U.S. (202 metric
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-7/16" (62 mm)
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Bulb: Glass, nominal 3 mm diameter
Pip Cap: Brass UNS-C31400 or UNS-C31600
Compression Screw: Brass UNS-C36000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order EC/QREC Ordinary Hazard Upright Sprinkler VK570 by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix (°F/°C): 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G, OPEN = Z (PTFE only).
For example, sprinkler VK570 with a Brass finish and a 155 °F/68 °C temperature rating = Part No. 13840AB.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 07297W/B (available since 1991)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971)
Form No. F_010104
18.10.11
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
)
*
Rev 18.3.P65
EC/QREC ORDINARY
HAZARD UPRIGHT
SPRINKLER VK570 (K14.0)
NOTE: As of May 2018 all logos have been removed from
the wrench boss.
Replaces Form No. F_010104 Rev 18.3
(Added P65 Warning.)
Page 1 of 5

Advertisement

loading
Need help?

Need help?

Do you have a question about the VK570 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Viking VK570

  • Page 1 Ordering Information: (Also refer to the current Viking price list.) Order EC/QREC Ordinary Hazard Upright Sprinkler VK570 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
  • Page 2: Technical Data

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 4. INSTALLATION Refer to appropriate NFPA Installation Standards.
  • Page 3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES...
  • Page 4 “Minimum Water Supply Requirement” used. For Sprinkler VK570 with High Temperature 286 °F rating, UL restricts the QR listing to their use in Ordinary Hazard occupancies to the high temperature zones within a building only. VK570 quick response sprinklers with this temperature rating cannot be used throughout the property.
  • Page 5 The sprinkler installation rules contained in NFPA 13 for extended coverage upright spray sprinklers must be followed with the exception that • cULus Listing requires the spacing between Viking ECOH Upright Sprinklers to be a minimum of 9 ft. (2.75 m) to prevent cold soldering. •...
  • Page 6 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 7 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 8 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 9 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 10 1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 11 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 12 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 13: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...

This manual is also suitable for:

K14.0