Haier GE NF96DS Installation Instructions Manual page 20

Warm air gas furnace downflow air discharge direct vent & non-direct vent
Hide thumbs Also See for GE NF96DS:
Table of Contents

Advertisement

Page 20 of 55
Pipe size determined in table 7.
2"
2"
2"
2"
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
Figure 22. Typical Exhaust Pipe Connections
Pipe size determined in table 7.
2"
2"
3"
TRANSITION
*2"
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
Figure 23. Typical Intake Pipe Connections (Direct Vent Applications)
2"
3"
TRANSITION
*2"
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
2"
2"
2"
or
NOTE: 1-1/2" Vent Pipe
Diameter Allowed Only
on 045/070 Units
1-1/2"
or
TRANSITION
*2"
Issue 2223
NOTE: 1-1/2" Vent Pipe
Diameter Allowed Only
on 045/070 Units
1-1/2"
or
TRANSITION
*2"
INTAKE
TOP VIEW
TRANSITION
*2"
3"
*2"
EXHAUST
TOP VIEW
INTAKE
EXHAUST
507769-05G / 31-5000656