Details of Exhaust Piping Terminations for Non-
Direct Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred.
Figure 38 through Figure 39 show typical terminations.
1.
Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed
in Table 13. The specified pipe size ensures proper
velocity required to move the exhaust gases away from
the building.
2.
On field supplied terminations for side wall exit, exhaust
piping may extend a maximum of 12 inches (305mm)
for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC
beyond the outside wall.
12" (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
3" (76MM) OR
2" (51MM) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
Figure 38. Non-Direct Vent Roof Termination
3.
If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, piping
must be supported every 24 inches (610mm). When
exhaust piping must be run up an outside wall, any
reduction in exhaust pipe size must be done after the
final elbow.
4.
Distance between exhaust pipe terminations on multiple
furnaces must meet local codes.
31-5000729 Rev. 0
SIZE PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
Page 35
* SIZE TERMINATION PIPE PER EXHAUST
PIPE TERMINATION SIZE REDUCTION TABLE
Minimum 12" (305mm)
above chimney top
plate or average snow
accumulation
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
NOTE − Do not discharge exhaust gases directly into any chimney
or vent stack. If vertical discharge through an existing unused
chimney or stack is required, insert piping inside chimney until the
pipe open end is above top of chimney and terminate as illustrated.
In any exterior portion of chimney, the exhaust vent must be
insulated.
Figure 39. Non-Direct Vent Application Using Existing
Chimney
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ge nf96d045s3bGe nf96d070s4bGe nf96d090s4c

Table of Contents