7. Normal operation
7.5.11.4 Backflow Work Mode
This submenu is used for set backflow work mode: 01, 02. "01" is the default mode.
->Backflow Work Mode
Figure 7.28 Set the Backflow work mode
YES=<ENT> NO=<ESC>
Mode "01", As shown in the figure 7.30, the average limiting mode, the output power of each
phase is the average of the three-phase load power, and it is more than the phase of the
lowest power in three phases.
Inverter
.54.
Mode:01
Figure 7.29
Meter
Figure 7.30
7. Normal operation
Mode "02", As shown in the figure 7.31 the per phase limiting mode, the inverter only
generate the power that equals to one of three-phase load power that is the lowest
load power of a certain phase.
Inverter

7.5.12 External EPM Set

This setting should only be turned on when Canadian Solar external EPM device is used.
Two options are available:5G-EPM and Others-EPM.
->5G-EPM
Others-EPM
5G-EPM Failsafe Option should be turned ON when 5G series EPM device is used
Others-EPM Failsafe Option should be turned ON when 2G series EPM device is used
Only one option can be activated each time.

7.5.13 Restart HMI

ThefunctionisusedforrestarttheHMI.
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Meter
Figure 7.31
Figure 7.32