3.1.5

AC Power Supply

The installer must connect AC power for the battery charger (which is integral to the RDC2 controller) and the optional
accessories shown in Figure 25. The power source must comply with state and local codes. The power to the battery charger
and accessories must be backed up by the generator so that power is available at all times.
Be sure to disconnect power at the distribution panel before making the connections. Connec t power leads to the AC power
connection points labeled LINE, NEUTRAL, and GROUND on the field-connection terminal block. Connect to a circuit that is fed
by the load side of the transfer switch, so that it is backed up by the generator. See the Field Connections section and the
wiring diagrams in the Drawings and Diagrams section for connection details.
Equipment
Battery charger (standard)
Carburetor heater (optional)
Battery heater (optional)
Fuel regulator heater (optional;
available for 18RCAL and
20RCA/RCAL only)
Figure 25
Power Requirements
36
Power Requirement, Max.
Watts
Volts at 50/60 Hz
50
100- 120 VAC
50
200- 250 VAC
37
100- 120 VAC
37
200- 250 VAC
50
100- 120 VAC
50
200- 250 VAC
60
100- 120 VAC
100
200- 250 VAC
TP-7091