6) Solid Red (No Devices Configured/Enabled) – There are no BACnet/IP servers that are
configured/enabled.
7) Solid Red (Empty Scan List) - One or more enabled BACnet/IP servers have no scan lines configured.
a) Verify there are scan lines configured for devices that are enabled.
8) Off – Ethernet cable is unplugged.
Variables - These are the values for All Servers or the specific server selected.
1) Network Bitmap Status (Displayed in Hex):
a) Each bit corresponds to a server. If the bit is set, the server is connected, otherwise the bit is 0.
b) Bit 0 corresponds to Server 1 and Bit 4 is for Server 5 and so on.
2) RD Prop Request– Number of Read Property Single requests sent to the BACnet/IP devices.
a) NOTE: Read Property Single Requests are only used if the BACnet/IP device does not support
Read Property Multiple (RPM).
3) WR Prop Request– Number of Write Property Single requests sent to the BACnet/IP devices.
a) NOTE: Write Property Single Requests are only used if the BACnet/IP device does not support
Write Property Multiple (WPM).
4) RD Prop Multiple Request– Number of Read Property Multiple requests sent to the BACnet/IP
devices.
5) WR Prop Multiple Request– Number of Write Property Multiple requests sent to the BACnet/IP
Devices.
6) RD/WR Response Success – Number of successful read or write responses received. This value
should be equal to RD Single + WR Single + RD Multiple + WR Multiple Variable Counts.
7) RD/WR Response Error – Number of read or write error responses received.
a) NOTE: If the gateway receives an error of Unsupported Service for a RPM or WPM request, then
RP/WR Single requests will be used for that device for the duration of that power up.
8) RD/WR Timeout – Total number of read/write requests sent to the BACnet/IP device with no reply
received within the response timeout configured.
9) # of Object Read Attempts – Total number of objects that the gateway attempted to read.
10) # of Object Write Attempts – Total number of objects that the gateway attempted to write.
Status Strings - These are the values for All Servers, or the specific server selected.
1) Last Error Code:
a) Last read/write reply error that the gateway received