Connecting The Drain Pipe; Wiring - Sinclair SDV5-56FA Installation Manual

Full dc inverter systems
Hide thumbs Also See for SDV5-56FA:
Table of Contents

Advertisement

6. CONNECTING THE DRAIN PIPE

6.1 Install the drainpipe of the indoor unit
The outlet has a PTI screw bread. Use sealing materials and a
pipe sheath (fitting) when connecting PVC pipes.
CAUTION
The drain pipe and connections of the indoor unit must be heat
insulated, or it attracts condensation.
A hard PVC binder must be used to connect the pipes. Ensure
there are no leaks.
When connecting to the indoor unit, do not put pressure on the
side of the indoor unit's pipes.
Avoid winding when the declivity of the drain pipe in the
downwards direction is over 1/100.
The total length of the drain pipe when pulled out must not
exceed 20 m. When the pipe is too long, install a prop stand to
prevent winding.
Refer to the Fig.8-1 for the installing the pipes.
1.5m~2m
Insulating
Downward declivity
material
lower than 1/100
Put as deep as possible
(about 10cm)
Downward declivity
lower than 1/100
6.2 Drainage test
Check whether the drainpipe is unhindered.
Newly built house should be tested before decorating
the ceiling.

7. WIRING

Specified power cables should be used. Do not apply any
pressure on the terminals that will be connected.
Improper connection may cause a fire.
Grounding must be properly done.
The grounding wire should be away from gas pipes, water
pipes, telephones, lightning rods or other grounding wires.
Improper grounding may cause electric shocks.
Wiring must be done by professionals. Use a separate
circuit according to national regulations.
If the wiring capacity is not enough, electric shocks or fire may
occur.
Bend
S shape
Fig. 6-1
VP30
1. Be sure to Install Current Leakage Protection Switch, Or
electric shock may occur.
2. Power cord is to be selected according to national regula-
tions.
3. An all-pole disconnection device which has at least a 3 mm
separation distance between all poles and a residual current
device (RCD) with a rating above 10 mA must be incorporated
in the fixed wiring according to national regulations.
4. Select and connect outdoor unit power cords according to the
outdoor unit installation manual.
5. Wiring should be away from high temperature components,
or the insulation layer of the wires may melt.
6. Use a wire clamp to fix the wires and terminal block after
connection.
7. Control wire should be wrapped together with heat insulated
refrigerant pipes.
8. Connect the indoor unit to power only after the refrigerant
has been vacuumed.
9. Don't connect the power wire to the signal wire connection
end.
7.1 The specification of power
TYPE (W)
Phase
Power
Frequency
& volt
Circuit breaker/fuse (a)
Indoor unit power wiring(mm2)
Ground
Indoor/outdoor
wiring(mm
connecting wire
Weak electric
2
(mm
)
signal
A disconnection device having an air gap contact separation
in all active conductors should be incorporated in the fixed
wiring according to the National Wiring Regulation.
Power (220-240V~ 50Hz/220-240V~ 50/60Hz)
IN DOOR UNIT
IN DOOR UNIT
IN DOOR UNIT
The reserved function is indicated in broken line table,users
can select it when necessary
6
CAUTION
Table 7-1
3600-14000W
1-PHASE
220-240V~ 50Hz
220-240V~ 50/60Hz
5/3
1.0
1.0
2
)
0.75
CAUTION
CENTRAL CONTROL
MONITOR(CCM)
OUTDOOR UNI T
The shield twisted-pair wire
CAUTION
5/5
COMPUTER
Fig. 7-1