8.4 Main board Code designation
0/1 definition of each dial code switch:
means 0
SW1 definition
0 means cooling mode temperature
compensation is 0°C (default)
1 means cooling mode temperature
compensation is 2°C
0 means EXV positions 96 (steps)
in standby in heat mode (default)
1 means EXV positions 72 (steps)
in standby in heat mode
SW2 definition
00 means external static pressure
mode 1 (default)
01 means external static pressure
mode 2
10 means external static pressure
mode 3
11 means external static pressure
mode 4
SW3 definition
0 means no action (default)
1 means clear indoor unit address
Reserved (defaults 0)
SW4 definition
00 means the time of stopping
TERMAL fan is 4 mintue (default)
01 means the time of stopping
TERMAL fan is 8 mintue
10 means the time of stopping
TERMAL fan is 12 mintue
11 means the time of stopping
TERMAL fan is 16 mintue
SW5 definition
means 1
SW6 definition
SW7 definition
J1 definition
8
00 means shutting down the unit to
"stop cold air" at 15℃(default)
01 means shutting down the unit to
"stop cold air" at 20℃
10 means shutting down the unit to
"stop cold air" at 24℃
11 means shutting down the unit to
"stop cold air" at 26℃
00 means temp. compensation value
is 6°C under heat mode (default)
01 means temp. compensation value
is 2°C under heat mode
10 means temp. compensation value
is 4°C under heat mode
11 means temp. compensation value
is 0°C under heat mode (follow me)
Reserved (defaults 0)
0 means low power setting
(1.8kW - 25.2kW) (default)
1 means high power setting
(28kW - 112kW)
Without jumper "J1" for auto restart
function
With jumper "J1" for manual restart
function