8. 3. Additional charging
Do not turn on the power unless all operations are complete.
After evacuating the system, add refrigerant.
Do not charge the system with a refrigerant other than R410A.
Always keep to the limit on the total amount of refrigerant. Exceeding the limit on
the total amount of refrigerant will lead to malfunction during charging of refrigerant.
Do not reuse recovered refrigerant.
Use an electronic scale to measure the charging amount of refrigerant.
Adding more refrigerant than the specified amount will cause a malfunction.
Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction.
Add refrigerant by charging the system with the refrigerant in the liquid state. If
the refrigerant cylinder is equipped with a siphon, it is not necessary to place the
cylinder upright.
8. 3. 1.
P rocedure for charging the system with refrigerant
1) Remove the charging cap from the liquid pipe. Use standard refrigeration prac-
tices when charging refrigerant.
2) Attach a charging hose to the refrigerant cylinder, and connect it to the charging
port.
3) Add refrigerant by calculating the additional refrigerant volume in accordance with
the calculation formula indicated below.
4) Remove the charging cap and install the charging hose.
5) Remove the body caps (gas pipe and liquid pipe), and open the valves.
6) Close the body caps.
7) After adding refrigerant, indicate the added charging volume on the unit.
* Tighten the body caps and charging caps to the torque values specified in the
Table A.
To open and close the valves, Use an M4 hexagon wrench for liquid pipe.
Use an M10 hexagon wrench for gas pipe.
* *
If you can not charge the specified amount of refrigerant with the above
method, be sure to charge the refrigerant through the gas pipe while operat-
ing in cooling mode. In order to prevent liquid back-flow, carefully operate
the refrigerant cylinder valve so that the refrigerant will flow in certain part at
a time.
8. 3. 2.
C hecking total amount of refrigerant and calculat-
ing the amount of refrigerant charge to be added
• The amount of refrigerant charge to be added is the total value of the basic refrig-
erant charge amount and the value calculated from the length of the liquid pipe.
• Round up the value to 2 decimal places.
Model
HP
Factory charged amount
AJH072LNLAH
8HP
AJH090LNLAH
10HP
AJH126LNLAH
14HP
Diameter of liquid pipe (mm)
Ø6.35
Ø9.52
Ø12.70
Ø15.88
Ø19.05
(1)
Calculation of additional amount for outdoor unit
a
Outdoor unit1 additional
A =
+
amount for outdoor unit
kg
a
Outdoor unit3 additional
=
amount for outdoor unit
kg
(2)
Calculation of additional amount for pipe length
Total length
of ø19.05 mm
liquid pipe
b × 0.268
B =
(kg/m)
m
kg
En-21
CAUTION
d
a
Additional amount for
(kg)
outdoor unit (kg)
11.20
0
11.20
0
11.80
3.30
b
Additional amount for pipe length (kg/m)
0.021
0.058
0.114
0.178
0.268
a
Outdoor unit2 additional
+
amount for outdoor unit
kg
Total
kg
Total length of
ø15.88 mm liquid
b × 0.178
pipe
+
+
(kg/m)
m
kg
Total length of
ø12.70 mm liquid
b × 0.114
pipe
+
(kg/m)
m
kg
Total length of
b
ø6.35 mm
× 0.021 (kg/
liquid pipe
=
m)
m
kg
(3) Calculation of additional charge refrigerant
C=A+B =
kg
(4) Calculation of factory charged amount
d
Outdoor unit1
D =
+
factory charged amount
factory charged amount
kg
Total
d
Outdoor unit3
=
factory charged amount
kg
(5) Total refrigerant amount check
E=C+D=
kg
Note : Check the total refrigerant amount under the following conditions
Condition
For 1 outdoor unit per refrigerant system
: Total amount of refrigerant ≤ 31.5kg
For 2 outdoor units per refrigerant system
: Total amount of refrigerant ≤ 63kg
For 3 outdoor units per refrigerant system
: Total amount of refrigerant ≤ 94.5kg
<Calculation>
• When there are 3 outdoor units (AJH126LNLAH , AJH090LNLAH, AJH072LNLAH)
connected to 1 system
(1) Calculation of additional amount for outdoor unit
A = 3.30 (kg) + 0 (kg) + 0 (kg) = 3.30 (kg)
(2) Calculation of additional amount for pipe length
If liquid pipe piping length is the following
ø
19.05 : 50m,
ø
15.88 : 25m,
ø
12.70 : 0m,
Additional charge volume B = 50 (m) × 0.268 (kg/m) + 25 (m) × 0.178 (kg/m)
+ 0 (m) × 0.114 (kg/m) + 20 (m) × 0.058 (kg/m)
+ 15 (m) × 0.021 (kg/m)
= 19.325kg
(3) Calculation of additional charge refrigerant
C = A + B = 3.30 (kg) + 19.33 (kg) = 22.63 (kg)
(4) Calculation of factory charged amount
D = 11.8 (kg) + 11.2 (kg) + 11.2 (kg) = 34.2 (kg)
(5) Check the total amount of refrigerant
When 3 outdoor units are connected to 1 system, the following condition must be
satisfied.
Condition: E = C + D ≤ 94.5 (kg)
Calculation: 22.63 (kg) + 34.2 (kg) = 56.83 (kg) < 94.5 (kg)
→ No problem if the above condition is satisfied.
Total length
of ø9.52 mm
b × 0.058
liquid pipe
+
(kg/m)
m
kg
Total
kg
(Round up C to 2 decimal place)
d
Outdoor unit2
+
kg
kg
Computational formula
E ≤ 31.5kg
E ≤ 63kg
E ≤ 94.5kg
ø
9.52 : 20m,