Vacuum process

Do not turn on the power unless all operations are complete.
If the system is not evacuated suffi ciently, its performance will drop.
Be sure to evacuate the refrigerant system using a vacuum pump.
The refrigerant pressure may sometimes not rise when a closed valve is opened after
the system is evacuated using a vacuum pump. This is caused by the closure of the
refrigerant system of the outdoor unit by the electronic expansion valve. This will not
aff ect the operation of the unit.
Use a clean gauge manifold and charging hose that were designed specifi cally for
use with R410A. Using the same vacuum equipment for diff erent refrigerants may
damage the vacuum pump or the unit.
Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.
• If moisture might enter the piping, follow below. (i.e., if doing work during the rainy
season, if the actual work takes long enough that condensation may form on the
inside of the pipes, if rain might enter the pipes during work, etc.)
• After operating the vacuum pump for 2 hours, pressurize to 0.05 MPa (i.e., vacuum
breakdown) with nitrogen gas, then depressurize down to -100.7kPa (-755mmHg)
for an hour using the vacuum pump (vacuum process).
• If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing
for at least 2 hours, repeat the vacuum breakdown - vacuum process.
After vacuum process, maintain the vacuum for an hour and make sure the pressure
does not rise by monitoring with a vacuum gauge.
Evacuation procedure
(1) Remove the blank caps of the gas pipe and liquid pipe and check that the valves
are closed.
(2) Remove the charging port cap.
(3) Connect a vacuum pump and a pressure gauge to a charging hose and connect it
to the charging port.
(4) Activate the vacuum pump and vacuum the indoor unit and connection piping until
the pressure gauge becomes -100.7kPa (-755mmHg).
Evacuate from both the gas pipe and the liquid pipe.
(5) Continue evacuating the system for 1 hour after the pressure gauge reads
-100.7kPa (-755mmHg).
(6) Remove the charging hose and reinstall the charging port cap.
8. 3.

Additional charging

Do not turn on the power unless all operations are complete.
After evacuating the system, add refrigerant.
Do not charge the system with a refrigerant other than R410A.
Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the
total amount of refrigerant will lead to malfunction during charging of refrigerant.
Do not reuse recovered refrigerant.
Use an electronic scale to measure the charging amount of refrigerant.
Adding more refrigerant than the specifi ed amount will cause a malfunction.
Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction.
Add refrigerant by charging the system with the refrigerant in the liquid state. If the
refrigerant cylinder is equipped with a siphon, it is not necessary to place the cylinder
upright.
Check if the steel cylinder has a siphon installed or not before fi lling. (There is an
indication "with siphon for fi lling liquid" on the steel cylinder.)
Filling method for cylinder with siphon
R410A
Set the cylinder vertical and fi ll with the
Gas
liquid.
(Liquid can be fi lled without turning bot-
tom up with the siphon inside.)
Liquid
Filling method for other cylinders
R410A
Turn bottom up and fi ll with liquid.
Gas
(Be careful to avoid turning over the
cylinder.)
Liquid
Be sure to use the special tools for R410A for pressure resistance and to avoid mixing
of impure substances.
If the units are further apart than the maximum pipe length, correct operation can not
be guaranteed.
Make sure to back closing valve after refrigerant charging. Otherwise, the compressor
may fail.
Minimize refrigerant release to the air. Excessive release is prohibited under the
Freon Collection and Destruction Law.
CAUTION
CAUTION
8. 3. 1.
Procedure for charging the system with refrigerant
(1) Remove the charging port cap from the liquid pipe.
(2) Attach a charging hose to the refrigerant cylinder, and connect it to the charging port.
(3) Add refrigerant by calculating the additional refrigerant volume in accordance with
the calculation formula indicated below.
(4) Remove the charging hose and install the charging port cap.
(5) Remove the blank caps (gas pipe and liquid pipe) and open the valves.
(6) Close the blank caps.
(7) After adding refrigerant, indicate the added charging volume on the unit.
* Tighten the blank caps and charging port caps to the torque values specifi ed in the
Table A.
To open and close the valves,
Use an M4 hexagon wrench.
8. 3. 2.
Checking total amount of refrigerant and calculating the
amount of refrigerant charge to be added
• The amount of refrigerant charge to be added is the total value of the basic refriger-
ant charge amount and the value calculated from the length of the liquid pipe.
• Round up the value to 2 decimal places.
Model
AJT040LCLAH
AJT045LCLAH
AJT054LCLAH
Diameter of liquid pipe (mm)
Ø6.35
Ø9.52
(1) Calculation of additional amount for pipe length
Total length of
a
ø9.52 mm liquid
× 0.058
pipe
A =
+
(kg/m)
m
kg
Total
=
(Round up A to 2 decimal place)
kg
(2) Calculation of total refrigerant amount
C = A + B =
kg
NOTE:
Check the total refrigerant amount under the following conditions
Condition
Total amount of refrigerant
<Calculation>
Outdoor unit: AJT054LCLAH
(1) Calculation of additional amount for outdoor unit
If liquid pipe piping length is the following
Φ9.52 : 20m , Φ6.35 : 10m
Additional charge volume:
A = 20 (m) × 0.058 (kg/m) + 10 (m) × 0.021 (kg/m)
= 1.37 kg
(2) Check the total amount of refrigerant
C = A + B = 1.37 kg + 4.0 kg = 5.37 kg ≤ 6.83 kg
→ No problem if the above condition is satisfi ed
8. 4.

Installing insulation

• Install insulation material after conducting the "8.1 Sealing Test".
• To prevent condensation and water droplets, install insulation material on the refriger-
ant pipe.
• Refer to the table to determine the thickness of the insulation material.
• If the outdoor unit is installed at a level that is higher than the indoor unit, the water that
has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit.
Therefore, use putty in the space between the pipe and the insulation to prevent the
entry of water.
B
Factory charged amount (kg)
4.0
4.0
4.0
a
Additional amount for pipe length (kg/m)
0.021
0.058
Total length of
a
ø6.35 mm liquid
× 0.021
pipe
(kg/m)
m
kg
(B : Factory charged amount)
Computational formula
C ≤ 6.83kg
En-18

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage ajt045lclahAirstage ajt054lclah

Table of Contents