The energy recovery module is factory assembled for
installation at the job site. It must match the cabinet size of
the MAPS
unit and may have a variety of control options.
®
MAPS
Cabinet Size*
®
A
B
C
*See cross-reference of MAPS
B, or C on page 11.
®
Installation, Operation, and Maintenance of
Option ER1A or ER1B for
MAPS ® Cabinet A or B
Installation of this energy recovery module should be done by a qualified agency in
accordance with the instructions in this manual and in compliance with all codes and
requirements of authorities having jurisdiction. The instructions in this manual apply to
energy recovery modules Option ER1A, ER1B, and ER1C, for MAPS
in Cabinet Sizes A, B, and C. Use this manual with the MAPS
Form I-MAPS III&IV, and operation/maintenance manual, O-MAPS-A/B/C.
There are warning labels on the module and throughout this manual. For your safety,
read the definitions below and comply with all paragraphs labeled CAUTION, WARN-
ING, and DANGER during installation, operation, maintenance, and service of this
energy recovery module as well as any other part of the MAPS
1. DANGER: Failure to comply will result in severe personal injury or
death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury
or death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury
and/or property damage.
Check for any damage that may have happened during shipment. If damage is found,
document the damage with the transporting agency and immediately contact your
Reznor distributor.
This module should be loaded and unloaded using all lifting points and spreader bars.
Do not attempt to move this module with a fork lift.
Option
Rating Plate Model
ER1A
ERMA
ER1B
ERMB
ER1C
ERMC
Models by Cabinet Size A,
®
Obsoletes I-MAPSIII&IV-ER (Version .2)
Option ER1, Energy Recovery Module
Applies to:
Outside
Air Hood
Option AS19
HAZARD INTENSITY LEVELS
A package of parts (P/N 262969) required
for installation is Included with each energy
recovery module:
Qty
P/N
2
260995
20
114687
40
11813
Form I-MAPSIII&IV-ER (Version .3)
MAPS
Series Models,
®
Cabinet Sizes A, B, and C
with Energy Recovery Module
Outside
Air Hood
Option AS19
®
unit installation manual,
®
system.
®
Description
Curb cap splice plates
1/4-20, 3/4" Screws (for
attaching splice plates)
#10-1/2" Sheetmetal screws
(for attaching cabinets)
I-MAPSIII&IV-ER, PN262634R3, page 1
Option ER1
Option ER1C
for MAPS ®
Cabinet C
III and IV units

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MAPS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Reznor MAPS Series

  • Page 1 Check for any damage that may have happened during shipment. If damage is found, document the damage with the transporting agency and immediately contact your Moving Reznor distributor. This module should be loaded and unloaded using all lifting points and spreader bars. Do not attempt to move this module with a fork lift.
  • Page 2: Dimensions And Weights

    3.0 Dimensions Dimensions of Energy and Weights Recovery Module for Option AS19, Top View MAPS ® III and IV, Dimensions Outside Cabinet Sizes A and B (see chart Air Hood below for (field assembled corner and installed) weights) 43-3/4 (1111) 64-1/16 (1627) Access Side View...
  • Page 3 4.0 Mounting A MAPS unit that includes an Optional ER1 energy recovery module requires an ® optional roof curb designed to include the field-attached energy recovery module. Roof on the Roof curb Option CJ34, CJ53, or CJ54 must be installed and the MAPS unit in place before ®...
  • Page 4 Lifting and Mating MAPS unit has color-coded ® the Energy Recovery connectors mounted in the wall Module and MAPS Unit ® for connecting energy recovery (cont’d) module control wires. Match the connector colors on the wires in the energy recovery module electrical compartment to the connectors on the...
  • Page 5: Dirty Filter Switch

    (Energy (Energy (Energy (MAPS® unit) (MAPS® unit) (MAPS® unit) Recovery Recovery Recovery Cabinet A, B, or C Cabinet A, B, or C Cabinet Outside Module) Module) Module) Outside Outside with Option ER1 with Option ER1 A, B, or C Outside Air & Option AR2J Option AR2L Option AR2K...
  • Page 6: Belt Tension

    Adjustable shutters allow the width of the bypass openings to be factory set to provide the percentage of bypass air needed as determined from the specifications provided on the order. If installation requirements change or if the bypass shutters are mistak- enly moved, contact the factory or Reznor representative for field adjustment. The ®...
  • Page 7: Checks Before Startup

    Optional Variable Frequency Drive and Controls - When an optional variable fre- quency drive is ordered, the motor will operate on varying speeds as determined by the electrical frequency. The energy recovery module may have a factory-installed VFD on the supply fan and/or the exhaust fan. Depending on which control was selected, the variable frequency drive on the supply fan is controlled by neutral pressure or constant volume (adjustable through the IQ controller).
  • Page 8: Maintenance And Service

    9.0 Commissioning Checks after Startup (cont’d) □ and Startup If equipped with dirty filter switch (Option BE28), set the switch. See Paragraph 6.0. (cont’d) □ After at least 8 hours but no longer than a week of operation, recheck the supply and exhaust fan components -- blower wheels including all set screws, blower pulleys, motor pulleys, and belt tension.
  • Page 9 According to the manufacturer, a wheel operating in a “clean” environment may not require annual cleaning, but a wheel in a “contaminated” environment may require mul- tiple cleanings a year to maintain airflow and recovery. The segmented design of the wheel not only provides for easier cleaning but also allows for replacement of individual dirty segments.
  • Page 10 10.0 Maintenance Checking the Wheel Seals - The seals are on the center support that goes across the diameter of the wheel. There are two seals on each side of the wheel with one seal on and Service each side of the hub. Seals are metal strips with insulation on the surface closest to the (cont’d) wheel.
  • Page 11 Cross Reference Models RDCB, Gas Heat Section Size Model Model RDDB, RDCC, RDCB RDCC of MAPS Models -100 -150 -200 -250 -300 -400 -500 -600 -700 -800 -1000 ® and RDDC and Cabinet Sizes by Gas Heat Section Size A, B, and C DX Cooling Models RCB * RDCB, RDDB, and RDB and DX Cooling...
  • Page 12 Energy Recovery Wheel (Maintenance) 8 Wheel Segments 9 Exhaust Fan 7 Filters 8 Frost Prevention 5 www.ReznorHVAC.com; (800) 695-1901 ©2014 Reznor, All rights reserved. ® Trademark Notes: Reznor and MAPS are registered in at least the United States. ® ®...

Table of Contents