Faults / Solutions

Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or incorrect
operation of the burner.
A fault usually makes the lockout led signal which is situated in-
side the reset push-button of the control box.
When the lockout lamp comes on, the burner will only attempt to
start up after the reset button has been pressed. If ignition is then
normal, the stop can be attributed to a temporary fault that is not
dangerous.
If however the lock out continues the cause must be determined
and the solution found.
Faults
The burner does not
start when there is heat
demand.
The burner goes into
lockout mode before or
during the pre-purging.
Burner runs normally in
the pre-purge and igni-
tion cycle and locks out
after 5 seconds ca.
Burner starts with an ig-
nition delay.
The manufacturer cannot accept responsibility for
any damage to persons, animals or property due
to error in installation or in the burner adjustment,
WARNING
or due to improper or unreasonable use or non
observance of the technical instruction enclosed
with the burner, or due to the intervention of un-
qualified personnel.
20071933
Possible cause
Lack of electrical supply.
The flame detector sees false light.
The connections in the control box
are wrongly inserted.
The P short-circuit socket is not con-
nected
The flame detector sees extraneous
light.
The flame detector is dirty.
The flame detector is faulty.
Flame moves away or fails.
The ignition electrodes are wrongly
positioned.
Air output is too high.
Nozzle dirty or worn.
Faults / Solutions
WARNING
DANGER
Fault
diagnostics
OFF
OFF
RED
Steady ON
OFF
28
GB
In the event of a burner lockout, more than two
consecutive burner reset operations could cause
damage to the installation. On the third lockout,
contact the Aftersales Service.
If further lockouts or burner faults occur, interven-
tions must only be made by qualified, authorised
personnel (as indicated in this manual, and in
compliance with the laws and regulations current-
ly in force).
Solutions
Check presence of voltage in the L - N the pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not lock out.
Eliminate the extraneous light.
Check and connect all the plugs and sockets prop-
erly.
Replace them.
Eliminate the extraneous light.
Clear it.
Replace it.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve.
Adjust them according to the instructions of this
manual.
Set the air output according to the instructions of
this manual.
Replace it.
Tab. D