Power Supply - Vision OPLC V350-35-TA24 Installation Manual

Hide thumbs Also See for OPLC V350-35-TA24:
Table of Contents

Advertisement

Thermocouple
Thermocouple 0: use Input 9 as
negative input and 10 as positive.
Thermocouple 1: use Input 7 as
negative input and 8 as positive.
RTD
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected
Analog Outputs
The 0V signal of the analog input and output must be connected to the controller's 0V.

Power Supply

The controller requires an external 24VDC power supply.
The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class 2/Limited Power.
6
V350-35-TA24, V350-J-TA24, V350-S-TA24, V350-JS-TA24 Installation Guide
Type Temp. Range
mV
-5 to 56mV
200 to 1820˚C
B
(300 to 3276˚F)
-200 to 750˚C
E
(-328 to 1382˚F)
-200 to 760˚C
J
(-328 to 1400˚F)
-200 to 1250˚C
K
(-328 to 2282˚F)
-200 to 1300˚C
N
(-328 to 2372˚F)
0 to 1768˚C
R
(32 to 3214˚F)
0 to 1768˚C
S
(32 to 3214˚F)
-200 to 400˚C
T
(-328 to 752˚F)
Wire Color
ANSI (USA) BS1843 (UK)
+Grey
+None
-Red
-Blue
+Violet
+Brown
-Red
-Blue
+White
+Yellow
-Red
-Blue
+Yellow
+Brown
-Red
-Blue
+Orange
+Orange
-Red
-Blue
+Black
+White
-Red
-Blue
+Black
+White
-Red
-Blue
+Blue
+White
-Red
-Blue
Transistor Outputs (pnp)
Unitronics

Advertisement

Table of Contents
loading

This manual is also suitable for:

Oplc v350-s-ta24Oplc v350-j-ta24Oplc v350-js-ta24

Table of Contents