Din Rail Mounting; Wiring Procedure - Vision OPLC V350-35-TA24 Installation Manual

Hide thumbs Also See for OPLC V350-35-TA24:
Table of Contents

Advertisement

Vision™ OPLC™
4. When properly mounted,
the controller is squarely
situated in the panel
cut-out as shown in the
figure to the right.
DIN-rail Mounting
1. Snap the controller onto
the DIN rail as shown in
the figure to the right.
2. When properly mounted,
the controller is squarely
situated on the DIN-rail
as shown in the figure to
the right.
Wiring
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire strand
Caution
to break.
Install at maximum distance from high-voltage cables and power equipment.

Wiring Procedure

Use crimp terminals for wiring; use 3.31 mm ² –0.13 mm² wire (12-16 AWG):
1. Strip the wire to a length of 7±0.5mm (0.270–0.300").
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with I/O lines used over an extended distance. Use
wire that is properly sized for the load.
The controller and I/O signals must be connected to the same 0V signal.
Unitronics