Dantel 46019 Installation & Operation Manual

Dantel 46019 Installation & Operation Manual

Summary alarm module

Advertisement

Quick Links

About this Practice:
This practice has been reissued to:
• Meet ISO 9001 requirements.
Reissued Practices: Updated and
new content can be identified by a
banner in the right margin.
Issue date: February 1998
Copyright 1998 by Dantel, Inc. • Dantel is a registered trademark of Dantel, Inc. • ISO 9001 Registered
46019 S
A
LARM

Table of Contents

Ordering Information ........................................................................... 2
General Description .............................................................................. 2
Circuit Description ............................................................................... 2
Application Information ....................................................................... 5
Installation ............................................................................................ 6
Operation .............................................................................................. 8
Technical Specifications ....................................................................... 9
Warranty ............................................................................................. 10
CAUTION
Install or remove modules from the shelf only when the power is off.
If you install a module in the shelf with the power on, the internal
circuitry may suffer damage and the product warranty will be void.
Remove and install circuit boards only in a static-safe environment
(use antistatic wrist straps, smocks, footwear, etc.).
Keep circuit boards in their antistatic bags when they are not in use.
Do not ship or store circuit boards near strong electrostatic, electromag-
netic, magnetic, or radioactive fields.
For more complete information on electrostatic discharge safety
precautions, refer to Bellcore
Printed in the U.S.A.
I
NSTALLATION
UMMARY
M
ODULE
(SAM)
46019-11
SUMMARY
ALARM
C/O
EXIST
NEW
ALARM
ON
OFF
ACK
LEVEL A
C/O
C/O
EXIST
EXIST
NEW
NEW
ALARM
ON
OFF
ACK
LEVEL B
ACK
COMM
RLY
ALL
C/O
EXIST
NEW
ALARM
ON
OFF
ACK
LEVEL C
C/O
EXIST
NEW
ALARM
ON
OFF
ACK
LEVEL D
B11-46019-11 REV__
TM
Technical Reference # TR-NWT-000870.
& O
M
PERATION
ANUAL
46019-0298 <90-00028>

Advertisement

loading

Summary of Contents for Dantel 46019

  • Page 1: Table Of Contents

    For more complete information on electrostatic discharge safety Issue date: February 1998 precautions, refer to Bellcore Technical Reference # TR-NWT-000870. Copyright 1998 by Dantel, Inc. • Dantel is a registered trademark of Dantel, Inc. • ISO 9001 Registered Printed in the U.S.A.
  • Page 2: Ordering Information

    ORDERING INFORMATION NOTE: This section lists the different options available for this product. To order any of the avail- able options, contact Dantel Inside Sales through our toll-free number, 1-800-432-6835. OPTION NUMBER FEATURES B11-46019-11 Summary Alarm Module (SAM) GENERAL DESCRIPTION...
  • Page 3 The regulated power supply operates on -21 to -56 VDC input power and provides ±12 VDC and +5 VDC output power for the SAM circuits. The ±12 VDC and +5 VDC ouptput power routes to edge connector pins for off-board use. 46019-0298 <90-00028>...
  • Page 4 CIRCUIT DESCRIPTION . 1 - F , 46019 SAM UNCTIONAL CHEMATIC LEVEL A CIRCUIT N.O. (TYPICAL FOR LEVELS B, C, AND D) VISUAL COMM. EXIST CONTACTS N.C. FOLLOW LATCH N.O. OUTPUT RELAYS LATCH N.C. AUDIBLE GATE CONTACTS O.C. O.C. ON / OFF...
  • Page 5: Application Information

    APPLICATION INFORMATION ig. 2 shows a 46019 Summary Alarm Module example application. A SAM in each alarm shelf gives local control of alarm status indicators. You can locate the external indicators (audible and visual) controlled by the SAM’s relays on another floor (for example, the central office).
  • Page 6: Installation

    If you don’t need that time-out feature, do not set any switches in the ON position. Straps determine whether the relays follow the inputs or the latch. . 3 - S , 46019 SAM WITCH AND TRAP OCATIONS FOLLOW LATCH CIRCUIT "A"...
  • Page 7 INSTALLATION 2. Wire the pin connectors. Wire the pin connectors in the shelf or housing. Refer to Fig. 4. . 4 - P , 46019 SAM ESIGNATIONS Level B, Audible Relay, Common Level A, Audible Relay, Common Level A, External ACO Level B, External ACO Level B, Audible Relay, N.C.
  • Page 8: Operation

    INSTALLATION HECKOUT To check the operation of the 46019 SAM, monitor the unit in a system: Apply an alarm at each input being used and observe the front panel for proper audible alarm, LED, and relay operation. Acknowledge the alarms with the ACK ALL button. Interrupt the alarm signaling with the ACO switches.
  • Page 9: Technical Specifications

    Common External Acknowledge Input To Operate 0 to +1.4 VDC Relay Contact Rating @ 30 VDC 2.0 Amps @ 125 VAC 0.5 Amps Physical Dimensions 1.4" x 6.0" x 5.6" Weight 10.75 ounces Operating Temperature Range 0° to 55° C. 46019-0298 <90-00028>...
  • Page 10: Warranty

    To ensure expedient processing of your order, provide a purchase order number and shipping and billing information when requesting an RMA number. Also, when the units are returned to Dantel, include a descrip- tion of the failure symptoms for each unit returned. Send defective equipment to: Dantel, Inc.

This manual is also suitable for:

B11-46019-11