Resetting the system:
Depending on the sequence of installation, some units may require a system reset. To reset, press and hold test switch on left
side of unit for 6 seconds.
NS
BATTERY:
The batteries supplied in this equipment are high quality maintenance-free Valve Regulated Lead Acid design.
Ambient temperature of electrical room where batteries are installed should be 25° C (77° F) for maximum battery performance.
Replace batteries when they no longer operate the load for 90 minutes.
Replace only with manufacturer supplied parts.
Properly dispose of or recycle the Lead-Acid battery.
Switched input
Utility
Unswitched
input
Neutral
Ground
UTILITY
Hot(120V)
Neutral
UNSWITCHED
SWITCHED
INPUT
OUTPUT
(LOAD)
SELECT THE
CORRECT
VOLTAGE
AT TB1
FIGURE 5
Tel: (888) 552-6467

SYSTEM RESET

MAINTENANCE

NORMALLY-ON OPERATION
Circuit configured to operate in Normally-On mode.
TB1 LOCATION
UNSWITCHED
INPUT
{
Configuration shown: 120V in // 120V out.
For 277V in // 277V out, connect utility hot wire to 277V position
INPUT
Unit shipped with assembled jumper in place.
Blue
CIRCUIT #1
SWITCHED
INPUT
Neutral
Hot
Fax: (800) 316-4515
Important:
Orange
Black
Red
TO OBTAIN
120Vac OUTPUT
CONNECT RED WIRE TO APPROPRIATE
CORRESPONDING OUTPUT VOLTAGE
NOTE: WIRING DIAGRAMS
SIMPLIFIED FOR ILLUSTRATION.
ACTUAL POSITION OF COMPONENTS
MAY VARY.
EMIU 1500W Mini Inverter
For 277 V output: red wire must
be removed from 120 V side of
terminal block and wired to 277 V
side of terminal block.
Orange
Black
TB1
Red
TO OBTAIN
277Vac OUTPUT
POSITION TO OBTAIN
11/22 750.2189 Rev. B
7/12