Troubleshooting Guide - ABB EMIU 1500W Instruction Manual

Mini inverter
Hide thumbs Also See for EMIU 1500W:
Table of Contents

Advertisement

STATUS
INDICATOR
SYMPTOMS
(LED)
Lamp load is ON
Lamp load is OFF
Lamp load is OFF, but the
unit is in Normally ON
LED GREEN
mode
ON Steady, not
flashing
-Lamp load is OFF
installation is Normally OFF)
-Lamp load is ON
installation is Normally ON)
Lamp load is ON
LED flashing
Lamp load is OFF
GREEN/
ORANGE
Lamp load is ON
LED flashing
Lamp load is OFF
GREEN/OFF
Lamp load is ON
Lamp load is OFF
LED steady
-Lamp load is OFF (if
OFF, not
installation is Normally
flashing
OFF)
-Lamp load is ON (if
installation is Normally ON)
LED RED
steady ON +
Inverter Error
GREEN LED
on PCBA
charger board
steady ON
Tel: (888) 552-6467

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE
PROBLEM
None, if unit is in Normally ON
mode.
None, if unit is in Normally OFF
mode.
Output fuses burned out.
Inverter module output fuse burnt
out.
(if
Power at primary AC input +
battery discharged (at LVD) + no
(if
reaction with test button.
None, if unit is in Normally ON
mode +Nexus option.
None, if unit is in Normally OFF
mode +Nexus option.
None, if unit is in test mode or is
sampling load.
Output fuses burned out.
Inverter module output fuse burnt
out.
No power at primary AC input + in
emergency mode.
No power at primary AC input +
emergency mode stop (battery
discharged).
Power at primary AC input +
battery discharged (at LVD) + no
reaction with test button.
In emergency or in test, no output
(Inverter switch OFF).
In emergency or in test, no output
(Inverter Failure).
In emergency or in test, output OK
(Inverter Sensing defect).
In emergency or in test, no output
(Inverter Failure).
Over temperature in emergency
or in test.
Over load in emergency or in test.
Fax: (800) 316-4515
CORRECTIVE ACTION
Unit is operating correctly.
Unit is operating correctly.
- Verify output is not overloaded.
- Verify there is no short circuit in the load.
- Replace fuses.
Check field wiring on mini-inverter. Ensure no voltage is being
applied to the output of the mini-inverter. Replace fuse.
- Remove primary AC input + disconnect
battery + wait minimum 10 seconds.
- connect battery + connect primary AC input.
=> unit will restart.
- if unit did not restart, call technical support at 1-(888) 552-6467.
Unit is operating correctly. Unit is not commissioned to the Nexus
system.
Unit is operating correctly. Unit is not commissioned to the Nexus
system.
Unit is operating correctly.
- Verify output is not overloaded.
- Verify there is no short circuit in the load.
- Replace fuses.
Check field wiring on mini-inverter. Ensure no voltage is being
applied to the output of the mini-inverter. Replace fuse.
Check position of breaker feeding the Mini Inverter in the breaker
panel. If breaker has tripped, check for overload or short circuit.
See "AC SPECS" on page 1.
- Remove primary AC input + disconnect
battery + wait minimum 10 seconds.
- connect battery + connect primary AC input.
=> the unit will restart.
- if unit did not restart, call for technical support at 1-(888) 552-6467.
Turn inverter ON/OFF switch to ON position.
(Switch is located on right end of inverter module.)
Check inverter control RJ12/RJ50 cable to make sure cable it is
properly connected.
Check if yellow wire is connected. If not, connect. Refer to figure 4.
Reset system (see page 7). If result is the same, replace inverter
module.
- Verify LED Over Temp/Fault is ON on the inverter.
- Verify fan is blocked or not working.
- Call technical support at 1-(888) 552-6467.
- Verify LED Overload/Fault is ON on the inverter.
- make sure the total load connected does not exceed the units
rated capacity. See note on page 1 above warranty information.