J1 Wiring - Digital In / Analog In

 

Built-In I/O

The I/O is mapped into OCS Register space, in three sep-
arate areas: Digital/Analog I/O, High-Speed Counter I/O, 
and High-speed Output I/O. Digital/Analog I/O location is 
fixed starting at 1, but the high-speed counter and high-
speed output references may be mapped to any open 
register location. 
 
Digital and Analog I/O Function Registers
Digital Inputs
Reserved
ESCP Alarm
Digital Outputs
Reserved
Analog Inputs
Reserved
Analog Outputs
Reserved

J2 Wiring - Digital Out

Wiring Details

Solid/Stranded Wire:   1 2-24 awg (2.5-0.2mm2).
Strip Length:   0 .28" (7mm).
Torque, Terminal Hold-Down Screws:   4 .5 – 7 in-lbs 
(0.50 – 0.78 N-m).
 
 

Analog Input Tranzorb Failure

A common cause of Analog Input Tranzorb Failure on Ana-
log Inputs Model 2, 3, 4 & 5: If a 4- 20mA circuit is initially 
wired with loop power, but without a load, the analog input 
could see 24VDC. This is higher than the rating of the tran-
zorb. This can be solved by NOT connecting loop power 
prior to load connection, or by installing a low-cost PTC in 
series between the load and analog input.
 
%I1-12
%I13-31
%I32
%Q1-12
%Q13-24
%AI1-2
%AI3-12
n/a
%AQ1-8
 
 