Ecs Features; Terms Used In This Manual - Honeywell Farenhyt ECS Series Manual

Emergency communication system
Table of Contents

Advertisement

Overview

1.2 ECS Features

Single enclosure for both Fire and Emergency Control System components
Onboard supervised microphone
Supports 25 Vrms or 70.7 Vrms speaker circuits using ECS-50W, ECS-INT50W, or ECS-DUAL50W. Supports 25 Vrms using ECS-
125W
Voice Control Module (ECS-VCM) and Network Voice Control Module (ECS-NVCM)
– IFP-100ECS, IFP-1000ECS, and IFP-2000ECS support one ECS-VCM.
– IFP-2100ECS or IFP-300ECS support one ECS-NVCM.
– Built-in Digital Message Repeater
– 15 one-minute ECS Messages
IFP-2000ECS, IFP-300ECS, and IFP-2100ECSsystems support dual-channel and backup audio using the ECS-DUAL50W amplifier
and ECS-50WBU backup amplifier.
SBUS Addressable Amplifiers
– IFP-100ECS, IFP-300ECS, and IFP-1000ECS systems support a combination of up to eight ECS-50W, ECS-125W or ECS-
DUAL50W amplifiers for a maximum of 1000 watts per system.
– IFP-2000ECS systems support up to 16 ECS-50W, ECS-125W, or ECS-DUAL50W amplifiers for a maximum of 2000 watts per
system.
– IFP-2100ECS has support for up to 16 ECS-50W, ECS-125W, ECS-INT50W, or ECS-DUAL50W amplifiers for a maximum of
2000 watts per system.
Local Operator Console (LOC)
– IFP-100ECS, IFP-300ECS, IFP-1000ECS, and IFP-2000ECS systems can support up to seven ECS-LOC consoles.
– IFP-2100ECS systems can support up to 15 ECS-2100LOC consoles.
Mappable Speaker Circuits
– IFP-100ECS, IFP-300ECS, and IFP-1000ECS systems can support up to 64 mappable speaker circuits using a combination of ECS-
50W, ECS-125W, ECS-DUAL50W amplifiers and ECS-CE4 expanders.
– IFP-2000ECS and IFP-2100ECS systems can support up to 128 mappable speaker circuits using a combination of the ECS-50W,
ECS-125W, ECS-DUAL50W, and ECS-INT50W amplifiers, and ECS-CE4 expanders.
Backup Amplifier
– ECS-DUAL50W amplifiers are capable of providing 50 watts of backed up audio power with the addition of the ECS-50WBU.
ECS messages can be selected as priority over fire.
Programmable trigger inputs from an external source, such as a Monaco system, to the ECS-NVCM, ECS-RVM, 5880, any SLC input
module, or Flexput module.

1.3 Terms Used in this Manual

The following terminology is used with the this system:
Term
ECS
FACP
LOC
Mass Notification
ECS Series
ECS Device
ECS Control
ECS Point
ECS LOC Priority
ECS Super User
VBUS
Module
Main control panel
8
Emergency Communication System: The features of the control panel and accessories that provide Mass Notification
functionality as described in UL standard 2572.
Fire Alarm Control Panel
Local Operator's Console: The user interface for a Mass Notification System. In the Honeywell Farenhyt Series
product line, this would be the interface provided by the IFP-100ECS, IFP-1000ECS, IFP-300ECS, IFP-2000ECS,
IFP-2100ECS, ECS-LOC, or ECS-LOC2100.
A way of protecting life by relaying specific event information to a building or site including voice and/or audible and
visual signals.
When this is used in a statement, it would indicate the that statement applies to the IFP-2000ECS, IFP-1000ECS,
IFP-100ECS, IFP-300ECS, and IFP-2100ECS control panels.
An ECS-LOC or an -5880 module that is programmed as an ECS device. These are used as inputs for triggering the
ECS on an IFP-100ECS, IFP-300ECS, IFP-1000ECS, IFP-2000ECS, and IFP-2100ECS.
ECS Control is a mode that all LOC units must enable to change the current state of the ECS system. ECS Control is
requested by using the ECS Control Button on LOC stations.
An input point that is programmed to trigger an ECS event on the IFP-2000ECS or IFP-2100ECS.
The priority level which is programmed for every ECS LOC. In order from lowest to highest, they are: Low, Normal,
High.
A user profile provided option that allows the user to override all ECS Control rules and gain ECS Control.
The VBUS is an analog voice bus that carries the recorded voice messages from the ECS-VCM/ECS-NVCM to the
ECS-50W, ECS-125W, or ECS-DUAL50W, or the voice messages generated from a system microphone to the ECS-
50W, ECS-125W or ECS-DUAL50W.
The term module is used for all hardware devices except for SLC addressable devices and notification appliances.
Refers to the IFP-100ECS, IFP-300ECS, IFP-1000ECS, IFP-2000ECS, or IFP-2100ECS control panel in the ECS
Series cabinet.
Description
ECS Series Manual — P/N 151455:H 2/15/2022
ECS Features