Honeywell Farenhyt ECS Series Manual page 40

Emergency communication system
Table of Contents

Advertisement

ECS Device Installation
Wiring Lengths
Number Of Speakers
@1/2 W
10
20
30
40
52
80
100
150
200
250
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed.
Class B
Figure 4.42 illustrates how to wire speakers to the control panel using Class B supervision.
Class A
Figure 4.43 illustrates how to wire speakers to the control panel using Class A wiring.
40
Total Load
@1 W
Vrms
Watts
5
25Vrms
5W
10
25Vrms
10W
15
25Vrms
15W
20
25Vrms
20W
26
25Vrms
26W
40
25Vrms
40W
50
25Vrms
50W
75
25Vrms
75W
100
25Vrms
100W
125
25Vrms
125W
Table 4.3 ECS-125W Wire Lengths
CIR CU IT 4
C IR C U IT 3
+
IN
+
O U T
+
IN
+
O U T
supervised,
power-limited
Figure 4.42 Class B Speaker Configuration
supervised,
power-limited
Figure 4.43 Class A Speaker Configuration
Wire Distance in Feet
18 AWG
16 AWG
3900
6200
2125
3380
1460
2320
1100
1750
760
1200
550
875
450
715
300
476
225
357
180
285
CIR CU IT 2
C IR CU IT 1
+
IN
+
O U T
+
IN
+
O U T
CIRC U IT 1
+
IN
+
O U T
ECS Series Manual — P/N 151455:H 2/15/2022
Installing the ECS-125W
14 AWG
12 AWG
9860
15680
5375
8540
3690
5870
2780
4420
1920
3050
1390
2200
1130
1800
753
1200
565
900
452
720
15kΩ EOL