CAST ZFP Analogue Addressable Fire Alarm Panel
8.6.6
Add New Device
NB: THIS MENU OPTION HAS TO BE SELECTED BEFORE A LOOP DEVICE IS ADDED .
Enter AL3 (4444) > Commissioning Functions > Add New Device.
Fit the new device at the selected unpopulated loop address.
The panel will then detect the new device and the following will be displayed, for example:
As shown above, press the device description display and the panel will ask for confirmation. Press the Accept
New Device? button and then you will be able to edit the selected device's parameters as shown in section 8.5.1.4.
8.6.7
Add/Delete/Edit a Device
Refer to Device Manager section 8.5.1 for details.
8.6.8
Edit Zone Name
This function allows the text description assigned to a zone to be edited.
Enter AL3 (4444) > Commissioning Functions press the
the one shown below left appears.
To change a zone's name, press the text description button ('Zone 1' is shown as an example) and the window
shown below right appears. Amend the text using the touchscreen's standard QWERTY keyboard controls.
To select a different zone for editing, either press the zone number field (001 shown below left) and use the
and
buttons to scroll through the zones, or enter the zone number directly into the zone number field
using the touchscreen's numeric keypad.
Installation and Programming Manual Approved Document No. DFU5030000 Rev 4 Page 46 of 60
In the next display (shown left) select a loop.
In the next display scroll through the loop devices and select an
unpopulated 'no device fitted'
The panel will display 'Waiting For Device'.
icon
button and a window similar to