Carrier TOSHIBA MMK-UP0301HP-UL Service Manual page 134

Mult type
Table of Contents

Advertisement

1
In the "Field setting menu" screen, press
[
] and [
] to select "Test mode", and
then press [
Test mode is set, and returns to the "Field
setting menu" screen. Press the [
button 2 times, to open screen (2).
2
Press [
ON/OFF]
Operation starts, and in test mode screen (1)
opens. (While stopped, it is screen (2))
Test mode is done while the operating mode is
set to "Cool" or "Heat".
The temperature cannot be set in test mode.
Check codes are displayed in the normal way.
3
After completing test mode, in the "Field
setting menu" screen, press [
[
] to select "Test mode", and then press
[
Set/Fix]
Screen (3) appears.
Press [
Set/Fix] to end test mode and do
normal operation.