Do not attempt to repair the RS-7000 sensor. In case of incorrectly functioning control, contact the nearest Johnson
Controls® representative, and specify the required product code number. When you contact the supplier for a replacement
please state the type or model number of the control located on the data plate or cover label.
IMPORTANT
• Use this RS-7000 sensor only as an operating control. Where failure or malfunction of the RS-7000 sensor could lead
to personal injury or property damage to the controlled equipment or other property, additional precautions must be
designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit
controls intended to warn of, or protect against, failure or malfunction of the RS-7000 sensor.
• Do not install this sensor in condensing, wet, or damp environment. Moisture may cause damage to the sensor.
• Do not remove PCB from the enclosure cover. Removal of the PCB from the enclosure cover voids the product warranty.
• Make all wiring connection in accordance with local, regional, and national regulations. Do not exceed the RS-7000
sensor electrical ratings.
• Remove LCD plastic cover before use.
WARNING
Disconnect power supply before you make electrical connections. Contact with components carrying hazardous voltages
can cause electrical shock and may result in severe personal injury or death.
• Risk of Electrical Shock and Property Damage: Insulate and secure each unused wire lead before you apply power
to the device. Failure to insulate and secure each unused wire lead may result property damage, electrical shock, and
severe personal injury or death.

SETUP AND ADJUSTMENT

Press
button for 5 seconds, to get in parameter list, press
button to change parameter value.
Item
Parameter
01
Display language
02
Units
03
Temperature setpoint adjustment type
04
W/C range max
05
W/C range min
06
Humidity display
(only for RS-7060-0000)
07
Default display
08
Backlight time
09
Setpoint high limit
10
Setpoint low limit
11
Keypad lock
12
Temperature offset
13
Humidity offset
P/N 24-11070-00019 Rev. D Issue Date: 03 2023
button to switch over setting items and use
Default
Function
00
00: Chinese
01: English
°C
C
F
00: Setpoint
00
01: W/C
3°C
0°C to 5°C (3 means SP+3), 0°F to 9°F
-3°C
-5°C to 0°C (-3 means SP-3), -9°F to 0°F
00
00: Enable
01: Disable
00
00: Room temperature
01: Setpoint temperature
02: Relative humidity (only when Humidity display is available)
30
05 to 60, reduce backlight after xx seconds
28°C
2°C to 40°C (36°F to 99°F)
12°C
0°C to 38°C (32°F to 95°F)
00
00: No lock
01: Lock all keys
02: Lock the key except occupancy
0°C
Setting range –5°C to 5°C (-9°F to 9°F)
0%RH
Setting range –10% to 10% RH
English