Siemens SIMATIC ET 200SP Manual page 41

Im 155-6 pn st interface module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interfaces
Number of PROFINET interfaces
1st interface
Interface hardware
Protocols
Interface hardware
RJ45 (Ethernet)
10 Mbps
100 Mbps
Transmission method
Autonegotiation
Autocrossing
Protocols
PROFINET IO
PROFINET IO
PROFINET IO device
Services
Open IE communication
TCP/IP
SNMP
LLDP
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
IM 155-6 PN ST interface module (6ES7155-6AU00-0BN0)
Manual, 12/2014, A5E03576904-AC
Number of ports
Integrated switch
BusAdapter (PROFINET)
PROFINET IO device
Open IE communication
Media redundancy
Open IE communication
IRT
PROFIenergy
Prioritized startup
Shared device
Number of IO controllers with shared device,
max.
Technical specifications
6ES7155-6AU00-0BN0
1
2
Yes
Yes; usable BusAdapters: BA 2x RJ45, BA 2x FC
Yes
Yes
Yes
Yes; for Ethernet services
Yes; PROFINET with 100 Mbps full duplex
(100BASE-TX)
PROFINET with 100 Mbps full duplex
(100BASE-TX)
Yes
Yes
Yes
Yes
Yes; with send cycles between 250 µs and 4 ms
in increments of 125 µs
Yes
Yes
Yes
2
Yes
Yes
Yes
No
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7155-6au00-0bn06es7155-6aa00-0bn0

Table of Contents