Power Board Initial Settings; Power Board Wiring; Wiring Procedure; Main Circuit Board - Panasonic CZ-CLNC1U Installation Instructions Manual

Lonworks interface
Table of Contents

Advertisement

Power Board Initial Settings

Not Install: Ordinarily, keep this set to "Not Install" (initial setting).
Install: Free topology terminal resistor (51Ω) for the
LonWorks communication lines.
Install
S002
Power board
CN005
(when AC 100-120V
power is connected)
100-120/200-240 V
50/60 Hz 1-PH
When AC 200-240V power is connected, connect the power
transformer primary-side to CN006. When AC 100-120V power is
connected, connect the power transformer primary-side to CN005.
(It is connected to CN006 when the unit is shipped from the plant.)

Power Board Wiring

LON communication
lines (2)
LON communication
line (2) (reserve)
LON communication
lines (1)
LON communication
line (1) (reserve)
Inter-unit
control lines
Inter-unit
control line (reserve)
Earth for power wiring
• The LonWorks communication lines can be connected
to either (1) or (2) in the above fi gure. The results are the
same.
• Do not run the inter-unit control lines, the LonWorks
communication lines, and the power cables through the
same conduit, or place the cables near one another. Doing
so can cause the system to malfunction.
• Before turning the power on, follow the instruction in Power
Board Initial Settings.
• When using the spare inter-unit cotrol line, connect [1] and [3]
at CN002.
• When using the spare LON communication line, connect [1]
and [3] or [4] and [6] at CN003.
Pana̲CZ-CLNC1U̲Eng.indd   5
Pana̲CZ-CLNC1U̲Eng.indd   5
Not Install
ON
Power switch
S001
OFF
CN006 (when AC 200-
240V power is connected)
Power transformer primary-side
6
CN003
Power board
1
3
L
N
CN002
1
100-120/200-240 V
50/60 Hz 1-PH

Wiring Procedure

• Connect the power supply lines to the L and N power supply
terminals.
(the power suplly neutral to the N terminal.)
• Connect an earth ground line to the screw.
Lon communication wiring
Power board
L
N
Inter-unit control wiring

Main Circuit Board

LD001~LD008
Neuron ID label
IC002
S005
S003
Address SW
LD009
S004
Indoor unit enabling SW
Conduit (Power cables)
S001
S002
Data
COM
S006
Setting SW
5
2011/11/11   12:23:42
2011/11/11   12:23:42

Advertisement

Table of Contents
loading

Table of Contents