4
Product description
4.1
EL2912 and EL2912-2200
The EL2912 is a safe output terminal with two fail-safe outputs, each with 2 A (24 V
The EL2912 meets the requirements of the following standards:
• EN 61508:2010 (SIL 3)
• EN 62061:2005/A2:2015 (SIL CL 3)
• EN ISO 13849-1:2015 (Cat. 4, PL e).
The TwinSAFE terminal has the typical design of a 12 mm EtherCAT Terminal. The outputs use the voltage
of the power contacts. In addition, the voltage of the power contacts is applied to terminal points 2/6 and 3/7.
The terminal points GND1, GND2 and GND U
Fig. 4: EL2912 - TwinSAFE terminal with two fail-safe outputs
EL2912 variants
The EL2912 has an integrated safety control that can be used for user-specific applications directly
on the component. The variant EL2912-2200 does not have this functionality and represents a pure
I/O component.
EL2912 and EL2912-2200
(terminal points 3/7) are directly connected internally.