KNX DALI Gateway
7 .  COMMUNICATION OBJECTS (continued)
7 .3 ETS parameter (continued)
7 .3 .2 Feedback
Enable "DALI line fault" object
Parameter enables "Fault gateway supply" object. This object is used
for reporting DALI gateway supply fault. Possible causes of the fault
are no mains connection to gateway supply terminal, power supply
malfunction or short circuiting DALI line more than 100ms. Please
check 7 .2 Communication Object Descriptions for detailed object
information.
Enable "Mains connection fault" object
Parameter enables "Fault mains connected" object. This object is
used for reporting a misconnection of mains to the DALI line.
Enable "Lamp fault" object
Parameter enables "Fault lamp" object. This object is used for
reporting whether there is any device that has a fault lamp is present
or not.
Enable "Device fault" object
Parameter enables "Fault ballast" object. This object is used for
reporting whether there is any offline or malfunctioned ballast/driver
is present or not.
Enable "Device status" object
Parameter enables "Device status" object. This communication object
is used for getting all current faults and states of a DALI device in one
comprehensive telegram.
Enable "Coded status switch" object
Parameter enables "Coded status switch" object. This object is used
to get switch status of a DALI group or an individual DALI ballast/
driver.
Enable "Coded status brightness value"
object
Parameter enables "Coded status brightness" object. This object is
used to get brightness value of a DALI group or an individual DALI
ballast/driver.
Enable "Coded faults" object
Parameter enables "Coded faults" object. This object is used to get
fault data of a DALI group or an individual DALI device.
Enable "Mains power failure status" object
Parameter enables "Main power failure status" object. This object is
used for reporting a no mains connection applied to the mains line of
0 026 99 KNX-DALI Gateway device.
Transmit mode description is the same for all parameters in Feedback
tab. But selections can be made independently for each parameter.
Transmit mode
"After request" option only response to a read request to status
object. "After change" mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Technical data sheet: S000114124EN-1
CONTENTS
enable
*disable
enable
*disable
enable
*disable
enable
*disable
enable
*disable
enable
*disable
enable
*disable
enable
*disable
enable
*disable
*after request
after change
after request or change
7 .  COMMUNICATION OBJECTS (continued)
7 .3 ETS parameter (continued)
7 .3 .3 Fault Condition
Lamp values on power on
Parameter defines the brightness value of ballasts when power on.
Lamp values on DALI voltage failure
Parameter defines the brightness value of ballasts on DALI line voltage
loss.
Lamp values on DALI voltage recovery
Parameter defines the brightness value of ballasts on DALI voltage
return.
Lamp values on KNX voltage failure
Parameter defines the brightness value of ballasts on KNX line voltage
loss.
Lamp values on KNX voltage recovery
(gateway reset)
Parameter defines the brightness value of ballasts on KNX voltage
return.
7 .3 .4 DALI Devices (1...64)
Dali devices must be enabled to control via switch, brightness or
relative dim communication objects.
Activate devices 1 – 16
Activate devices 17 – 32
Activate devices 33 – 48
Activate devices 49 – 64
Dali device count can be selected in this page. This page only activates
the DALI device control objects. Unselected device adresses can still
be controlled in scenes.
7 .3 .4 .1 Device 1...64
Switch status response mode
Switch status of the group can be read from this object itself or
separate status object. "No response" option disables the "Read" flag
of object.
"After request" mode; status object only response to a read request.
"After change" mode; status object always sends its status when
changed. If both selected; object will send the status with a change
and response to read requests.
Brightness value status response mode
Brightness value status of the group can be read from this object itself
or separate status object. "No response" option disables the "Read"
flag of object.
"After request" mode; status object only response to a read request.
"After change" mode; status object always sends its status when
changed. If both selected; object will send the status with a change
and response to read requests.
Updated:
Cat. No(s): 0 026 99
0 %(0)...100 %(255)
*value before power off
0 %(0)...100 %(255)
*no change
0 %(0)...100 %(255)
*no change
0 %(0)...100 %(255)
*no change
0 %(0)...100 %(255)
*no change
*no
yes
*no
yes
*no
yes
*no
yes
*no transmission
after request
after change
after change or request
*no transmission
after request
after change
after change or request