Download Print this page

Power Ok Led; Operation - LEGRAND 0 026 99 Technical Data Sheet

Knx dali gateway

Advertisement

KNX DALI Gateway
4 . CONNECTION
DALI

5 . OPERATION

5 .1 Description of the device
Operating Led,
Green
DALI Status Led,
Yellow
Manual Led,
Red
Technical data sheet: S000114124EN-1
CONTENTS
. . .
DALI
DALI
x 64
max.
0 026 99
=
29 V
Manual Button
Test Button
KNX programming button
KNX programming led
5 .  OPERATION (continued)
5 .2 Operation and Display

Power OK LED:

• OFF: KNX BUS failure.
• ON: KNX BUS connected.
DALI Status LED:
• OFF: No problem.
• ON: DALI line failure. Possible causes; mains supply failure, DALI line is
short-circuit, mains power is connected to DALI line.
• Slow Blink: A DALI device fault is present. (Fault lamp, fault ballast, ...)
• Fast Blink: Initialization is active.
Manual LED: Lights up when manual control is activated by pressing
manual button.
Manual Button: Activate/Deactivate manual control. (Press the manual
button for 3 seconds to activate. Press shortly to deactivate manual
control.)
Note: KNX commands cannot operated when manual control is
activated.
Test Button: If manual operation is activated, short press sends
broadcast on/off command and long press sends broadcast dim up/
down command to DALI line. (Commands are sent in sequent.)
Programming LED and Button: Physical address localization.
6 . STANDARDS
• Type of protection: EN 60529
• Safety class III: IEC 61140
• CE: In accordance with the EMC guideline and low voltage directives
Updated:
Cat. No(s): 0 026 99
Created: 11/01/2023
3/9