Electrical Data, 30Gx And 30Hxc Compressors, Option 150 + 150A - Carrier 30GX Installation, Operation And Maintenance Instructions

Screw compressor water-cooled liquid chillers and air-cooled liquid chillers
Table of Contents

Advertisement

5.3 - Electrical data, 30GX and 30HXC compressors, option 150 + 150a

Reference
size
06Na2146s7N
39
46
06Na2174s7N
06Na2209s7N
56
06Na2250s7N
66
06Na2300s5N
80
06Na2300s5E
80+
legend
06NA
- Compressor for air-cooled units
N
- Non-economized compressor
E
- Economized compressor
I nom.
- Average current draw of the compressor at Eurovent conditions (A)
MHA
- Must hold amperes (maximum operating current) at 360 V (A)
LRA
- Locked rotor current with across-the-line start (A)
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode) (A)
LRA (S) 1 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp.
- Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit
I nom.
MHa
72
99
87
124
103
148
124
177
149
207
174
258
lRa
lRa (y)
605
191
715
226
856
270
960
303
1226
387
1265
400
lRa (s) 1 cp.
lRa (s) 2 cp.
NA
NA
NA
NA
330
480
435
575
490
610
510
660
19