The pertinent safety requirements of DIN, EN, DVGW, TRGI, TRF and VDE, • ÖNORM, EN, ÖVGW-TR Gas, ÖVGW-TRF and ÖVE, • SEV, SUVA, SVGW, SVTI, SWKI and VKF • and all new and regionally applicable regulations and standards Manual LogoMatic G2...
Instructions for working on the system and system parameters • Disconnect the system from the mains and monitor it to ensure that no voltage is being supplied (e.g. at the separate cut-out or a main switch). • Secure the system against being restarted. •...
Use of the device without legible warning and information signs Use of the device in a defective condition 1.2 Device designation Designation: LogoMatic G2 Function: Transfer of thermal energy to the heating supply and hot water preparation Type: Prefabricated/complete stations as S-/M-/L-Line in different versions (UC, MC, MC-UC) Manufacturer: Meibes System-Technik GmbH Manual LogoMatic G2...
1.3 Information on hazards The safety and warning information draws attention to residual hazards that cannot be avoided due to the design and construction of the device. Please always observe the measures shown for avoiding these hazards. Never alter or modify the station by yourself. Such work may only be carried out by qualified specialist personnel.
These installation and operating instructions must be given to the customer. The technician carrying out and/or authorising the work (e.g. installer) must explain the functioning and operation of the system to the customer in a readily comprehensible way. Manual LogoMatic G2...
2. Functional description The electronically controlled LogoMatic G2 heat interface stations provide a residential station with domestic hot water and heating. The domestic water is heated via a stainless-steel plate heat exchanger and electronic control valves based on the continuous flow principle. The station must simply be connected to the flow and return lines and the cold water line.
3. LogoMatic G2 - electronically controlled heating interface station 3.1 Article numbers for prefabricated stations Art. no. keys for Logomatic G2 prefabricated stations Example: Identification Model Unit characteristic/ abbreviation Art. no. number for an unmixed HC for a mixed HC MC-UC...
Max. differential pressure(primary): 2.5 bar Min. differential pressure(primary): 0.03 bar The factory setting of the differential 10 kPa pressure regulator: Max. temp. (sanitary) 100 °C Permissible nominal pressure rating PN10 (sanitary): Min. operating pressure (sanitary): 1 bar Manual LogoMatic G2...
3.3 Design and components example representations: LogoMatic G2 MC-UC, insulated version LogoMatic G2 MC-UC, steel version e.g. with optional ball valves e.g. as DWC version Legend Components Comment Plate heat exchanger, stainless steel, copper soldered/copper 24 / 40 /60 plates...
Page 14
Hydraulic diagram LogoMatic G2 MC-UC-DHWC LogoMatic G2 UC (e.g. with optional DWC) Primary Primary Legend: Connections ¾" MT (without optional ball valves) MC-UC Cold water outlet for dwelling, (second CW connection) Domestic hot water outlet for dwelling (HW) Cold water inlet building connection (CW)
3.4 Installation Please follow the safety instructions in this document and any additional assembly instructions of other components during installation! Installing and operating the stations incorrectly will invalidate any warranty claims. Installation options: depending on variant, either surface- (SM) or flush-mounted (FM) on a wall. Note: for FM variants, optional insulating plates and strips are available separately.
Page 16
Unit dimensions and connections:(including example representations) LogoMatic G2 MC-UC-SI LogoMatic G2 MC-UC-DHWC-FS (shown with insulation, without front covers) (Variant with DWC) (without 110 mm) Note: For the connections legend, see chap. 3.3 For information on installation depths with different equipment and product combinations, see chapter 4.10.6.2.
3.4.1 Insulated surface-mounted variants with multi-part thermal insulation Dimensions of SM thermal insulation and retaining plate (in mm): We reserve the right to change designs and technical specifications of our products.
Page 18
Construction and installation steps Attach retaining plate to wall Carry out hydraulic and electrical connections (observe the following dimensions) Commissioning (see chap. 5) Hang LogoMatic G2 station with rear Attach front insulation parts insulation and stabilisation plate on retaining plate Legend Pos.
Page 19
Drill hole dimensions for station installation (for insulated SM variant) and use of optional mounting rail (M10203.762, see also chap. 4.10.5) with throughflow ball valves: Note: The connections (drinking water, heating) are each labelled with the appropriate symbol. Warning! Use plastic plugs only to fix the ball valves.
The heat meter may only be installed once the entire heating system has been flushed through. LogoMatic G2 stations are fitted with an adaptor (L = 110 mm, 2 x 3/4") for a heat meter which must be removed before the heat meter is installed.
4.2 Optional domestic cold water meter installation LogoMatic G2 stations are fitted with an adaptor (L = 110 mm, 2 x 3/4") for a cold water meter that must be removed before the cold water meter is installed. The corresponding instructions for the water meter must be followed.
Variants depicted: UC / MC-UC FL RL Reference value diagram(setting curves) for setting the zone valve (Kvs = 1.8): Volume flow[l/h] Please notice the separately enclosed installation instructions when for the living space control which is optionally available. Manual LogoMatic G2...
4.3.1 Optional safety temperature limitation and actuator STL safety temperature limitation (as contact thermostat) and 230 V electrothermal actuator (NC) as optional accessories: Technical data – STL Adjustment range: 20 – 90 °C The safety Switched power: 16 (2.5) A, 250 V temperature limiter (STL) interrupts the power supply to the pump if the set temperature is Temp.
Adjust the value by screwing the spindle in or out with an open-ended spanner (11 mm). Factory setting: closed (fully turned in, right stop) Note: When using an optional HFM, the volume flow transferred via the therm. circulation bridge is not taken into account. Manual LogoMatic G2...
4.5 Differential pressure regulator The differential pressure regulator is used for the hydraulic balancing of the heating circuits. Variants depicted: UC / MC-UC Setting with 4-mm hexagon socket wrench To adjust the differential pressure regulator, rotate the hexagon socket wrench anticlockwise until the end point is reached and the spring is fully released.
Page 26
The manufacturer-specific documents for the valve must also be observed! Manual LogoMatic G2...
4.7 Mixed heating circuit (depending on variant) Note: Function available only for LogoMatic G2 MC variants • Mixing circuit as injection system • MC variant with (P1) HE pump and (V4) zone valve for e.g. underfloor heating circuits Configuration: four-wire...
Minimum supply pressure: 0.05 MPa MAX. 0.52 Media temperature: +2 to +110 °C The LEDs (one red/green and 4 yellow) indicate the corresponding operating/alarm status. Please observe the respective information provided by the pump manufacturer. Performance characteristics: Manual LogoMatic G2...
4.8 Hot water throttle LogoMatic G2 stations (only S- and M-Lines) are fitted with a hot water throttle in the connecting pieces of the plate heat exchanger. The model with gasket simplifies the exchange process.
Note: The safety fuse of the sanitary installation in a dwelling with a domestic water circulation connection must comply with DIN 1988, i.e. with a safety valve and, if necessary, an expansion vessel. Manual LogoMatic G2...
Page 31
Pump characteristic curve of optional DWC pump: We reserve the right to change designs and technical specifications of our products.
4.10.1 Heating circuit manifolds Manifold variants Standard: 3 - 8 heating circuits (SI/FS), wide version 9-12 HC Features Emptying, bleed valve in the flow and return line, max. 6 bar Flow rate limiter 0.5 - 5 l/min M30x1.5 valve inserts with manual adjustment caps Stainless steel manifold mounted on base plate Connections G ¾"...
12 HC / zones MB-10560.07 SM insulated variants (SI) with prewiring concept up to 8 HC / zones MB-10560.08 Warning: The actuators needed in each case corresponding to the number of underfloor heating circuits must be ordered separately! Manual LogoMatic G2...
4.10.3 Static heating circuit (with MC-UC variants) and simultaneous heating circuit distribution Sample depiction of extension of the static heating circuit (UC-L) with ¾" MT connection with LogoMatic G2 MC-UC-SI variants with LogoMatic G2 MC-UC-FS variants (surface-mounted version (surface-/flush-mounted version as sheet as insulated housing)
Art. No.: M10203.762 Art. No.: M10203.749 in each case incl. 7x ¾" straight-way ball valves, seals, plugs and the circuit diagram Note: Please use plastic plugs only to fix the ball valves. Manual LogoMatic G2...
4.10.6 Cover hoods and cladding housing 4.10.6.1 Overview of SM hoods (S or SM) Example representations Fig. SM, dimensions in [mm] Height A Width B Depth C Notes Standard surface-mounted hood, coated steel, white (RAL 9016) Art. no.: M11100.11 Note: For wireless use, select plastic variant (-K).
Page 38
(Design for wide UFH manifolds) Plastic design: Art. no.: M11100.29K Height Height-adjustable feet with cover trim adjustable from: 100 to 170 mm Art. no.: M11100.71 Note: One additional factory-supplied thermal insulation pack per FM hood is available, art. no.: M66306.667 Manual LogoMatic G2...
M11114.61MKUPSX 8MC-UC M11114.81MKUP M11114.81MKUPSX (see example III) I) LogoMatic G2 UC-SI, M-Line, with ball valves component list (I) or as complete station CS: M11114.1HKAP Pos. Designation Art. no. (example) LM G2 prefabricated station as SI (SM), M-Line, UC, without DWC M11114.44...
Page 40
LogoMatic G2 MC-UC-SI, M-Line with 8x UFH manifold, connection group for stat. HC Component list (II) or as complete station CS: M11114.81MKAPSX Pos. Designation Art. no. (example) LM G2 prefabricated station as SI (SM), M-Line, MC-UC, without DWC HE pump for MC circuit M11114.642...
Page 41
III) LogoMatic G2 MC-UC-SF, M-Line with 8x UFH manifold, connection group for stat. HC Component list (III) or as complete station CS: M11114.81MKUPSX Pos. Designation Art. no. (example) LM G2 prefabricated station as SF (SM/FM), M-Line, MC-UC, without DWC M11114.612...
Please observe the instructions, benchmarks and settings for the control fittings specified in our service log when commissioning. The LogoTronic HIU controller must be connected to the power supply at all times when the system is full, especially for the pumps and actuators. Manual LogoMatic G2...
The following requirements must be met for successful commissioning: All components of the system are installed and assembled. The entire system is leak-tight. All necessary electrical connections have been made. A terminal device (tablet / smartphone) is available with the Flamconnect app installed. This free app is required for further settings/configurations on the controller.
7. Pressure loss characteristic curves Note: Please refer to our current LogoMatic G2 product brochure for performance diagrams. Pressure loss on the secondary side of the device (hot water section) in dependence on drawn off domestic water volume S-Line M-Line...
Page 45
Pressure loss on the primary side of the device in dependence on hot water flow rate * S-Line M-Line L-Line Domestic water draw-off rate [l/min] *Adaptor for HFM, valve fully open Pressure loss on the heating side of the device in dependence on hot water flow rate * Mixed HC Domestic water draw-off rate [l/min] *Adaptor for heat flow meter, pump and differential pressure regulator, valve und zone valve...
Check cold water throttle/flow limiter for domestic water Check target settings in the LogoTronic HIU controller and at the components Check functionality of all components Check performance of components against required performance Check functionality of backflow preventer Check switched heat demand Manual LogoMatic G2...
Page 49
We reserve the right to change designs and technical specifications of our products.
Page 50
Copyright Flamco B.V., Almere, the Netherlands. No part of this publication may be reproduced or published in any way without explicit permission and mention of the source. The data listed are solely applicable to Flamco products. Flamco B.V. shall accept no liability whatsoever for incorrect use, application or...
Need help?
Do you have a question about the LogoMatic G2 and is the answer not in the manual?
Questions and answers