2.2.15 Frame R4, Main cooling fan

Types:
ACX580-01-062A-4
ACX580-01-073A-4
ACX580-01-075A-2
ACX580-01-076A-2
ACX580-01-052A-4
ACX580-01-065A-4
ACX580-01-077A-4
The main cooling fan is located at the bottom of the drive. Replace the fan as follows:
a. Release the locking clamp, use a flathead screwdriver to assist
b. Remove the fan by opening the unit (1.) and pushing leftwards at the base (2.)
c. Clean the cooling air duct and the heat sink with compressed air.
See separate instructions in section 2.1.1
d. Check that the fans blowing direction is inside the unit and install
the new fan unit simply by pushing it to its place.
Ensure the fan operation when the drive is powered up
© Copyright 2018 ABB Oy. All rights reserved. Specifications subject to change without notice.
On-Site Service Instructions
ACx580-01 R0-R5