7.2

RS-485 serial port

The Delta Battery Backup features an RS-485 serial port for remote monitoring.
7.2.1 Technical specifications
RS-485 port specifications
Interface
RS-485
Baud rate
19200
Data bit
Stop bit
Parity
Slave address
7.2.2 Mapping of registers
Reading register
Register 0
Battery voltage
Battery voltage in tenths of a volt
Register 1
Alarms
BIT 00
No Power Network
BIT 01
Inverter Fault
BIT 02
Load Alarm
BIT 03
Battery Alarm
BIT 04
-
BIT 05
-
BIT 06
-
BIT 07
-
BIT 08
-
BIT 09
-
BIT 10
-
BIT 11
-
BIT 12
-
BIT 13
-
BIT 14
-
BIT 15
Test OK
7.2.3 Running a system test
The test activates the auxiliary output for 20 seconds. At the end of this period, BIT 15 of the Reading Register will be set to 1.
8
1
No
2
Writing register
Register 0
BIT 00
01992 523 523 info@deltamembranes.com www.deltamembranes.com
7. Remote monitoring
Commands
Run test
22