7. Remote monitoring
The Delta Battery Backup can be remotely monitored via four volt-free contacts, or an RS-485 serial port.
Please note, the colours of the cores
are for illustrative purposes only.
Actual colours will depend on the
cable used by the installer.
High level alarm
volt-free contact
No mains power
volt-free contact
Battery fault
volt-free contact
Anomaly load
volt-free contact
7.1

Volt-free contacts

The Delta Battery Backup features four volt-free (dry) contacts for connection to external devices such as a dial-out telemetry or
a building management system.
The volt-free contacts are intended for use with low voltage (SELV/ELV) circuits operating at a maximum of 1 amp.
The contacts can be either Normally Closed (NC) or Normally Open (NO) depending on the requirements of the system it is
connected to.
21
Delta Battery Backup
12V input
NC
C
K3
High level
alarm relay
NO
NC
C
K4
No mains
power relay
NO
NC
C
K5
Battery
fault relay
NO
NC
C
K6
Anomaly
load relay
NO
Figure 17. Remote monitoring connections.
RS485
COM
RS-485 serial port
B
A
+12V
DMS_IG_DBB 0123