Download Print this page

Panasonic M1S Series Operating Instructions Manual page 13

For speed control of 3-phase induction motor low-noise inverter

Advertisement

Applicable peripheral equipment
Wiring apparatus selection
(1) Selection of no-fuse breaker, magnetic contactor, thermal relay, (Matsushita Electric
Works No.) and wiring
Inverter No. Applicabl
e motor
(kW)
MIS011***
0.1
MIS021***
0.2
MIS041***
0.4
2
MIS01
***
0.1
3
2
MIS02
***
0.2
3
2
MIS04
***
0.4
3
2
MIS08
***
0.75
3
Use the same size of wire for GND terminal ( ) as the wire for main circuit.
(2) Relay selection
For relays used in control circuits such as the control input terminal, you should use a
small signal relay (min. guaranteed current of 1mA or less) in order to prevent poor
contact.
<Examples> Matsushita Electric Works: DS type, NK type, HC type
(3) Control circuit switch selection
If using a switch instead of a relay, use a switch for extremely small current in order to
prevent poor contact.
<Example>
*1
Motor cable is used if the distance between inverter and motor is 20 meters or less. If more than 20 meters,
use a larger cable.
No-fuse
Magnetic
breaker
contactor
(Rated current)
(Contact configuration)
BBP25
BMFT61842N
(5A)
(3P+1a)
BBP35
BMFT61842N
(5A)
(3P+1a)
BBP310
BMFT61842N
(10A)
(3P+1a)
BBP35
BMFT61842N
(5A)
(3P+1a)
BBP35
BMFT61842N
(5A)
(3P+1a)
BBP35
BMFT61842N
(5A)
(3P+1a)
BBP310
BMFT61842N
(10A)
(3P+1a)
Omron:
Nihon Kaiheiki:
‑ 13 ‑
Thermal
relay
(Current adjustment range)
BMF902E
(0.95〜 1 .45A)
BMF904E
(1.7〜 2 .6A)
BMF907E
(2.8〜 4 .2A)
BMF901E
(0.5〜 0 .75A)
BMF902E
(0.95〜 1 .45A)
BMF904E
(1.7〜 2 .6A)
BMF907E
(2.8〜 4 .2A)
G2A type
M-2012J-G
2
*1
Wiring (mm
)
Main
Control
circuit
circuit
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)
2.0
0.75
(AWG14)
(AWG18)

Advertisement