Huawei SUN2000 M5 Series User Manual page 47

Hide thumbs Also See for SUN2000 M5 Series:
Table of Contents

Advertisement

SUN2000-(12KTL-25KTL)-M5 Series
User Manual
grid when an exception occurs, select a proper overcurrent protection device in
compliance with local power distribution regulations.
● Do not connect loads between an inverter and an AC switch that directly
● If an AC switch is used with specifications beyond local standards, regulations,
Each inverter must be equipped with an AC output switch. Multiple inverters
cannot connect to the same AC switch.
The inverter is installed with an integrated monitoring unit for the residual
current. When the inverter detects that the residual current exceeds the permitted
value, it disconnects from the power grid quickly.
● If the external AC switch has residual current protection, its rated leakage
● If multiple inverters are connected to the master leakage protection device
● The AC switch cannot be a knife switch.
COM Port Pin Definitions
● When laying out signal cables, separate them from power cables and keep
● Ensure that the protection layer of a signal cable is inside the connector, that
Issue 03 (2023-02-15)
WARNING
connects to the inverter. Otherwise, the switch may trip by mistake.
or the Company's recommendations, the switch may fail to turn off in a timely
manner in case of exceptions, causing serious faults.
CA UTION
NO TICE
tripping current must be greater than or equal to 300 mA.
through their AC switches, the rated leakage tripping current of the device
must be greater than or equal to the number of inverters x 300 mA.
NO TICE
them away from strong interference sources to avoid strong communication
interference.
excess core wires are cut off from the protection layer, that the exposed core
wires are totally inserted into the cable hole, and that the cable is connected
securely.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Electrical Connections
41