1. GENERAL DESCRIPTION
The MD3300MRP device is designed to control electrical loads so as to
prevent, in case of simultaneous switching on of several devices, an overload
that may cause the maximum electrical energy consumption allowed by the
supplier to be exceeded and consequently the mains power supply to be
disconnected. For proper operation of the device it is necessary to:
• assign one or more MTR2000ERP(X) or MTR2000MRP(X) radio receiver
relays to the MD3300MRP device (up to 7 relays directly connected or
more than 7 using the RADIO BUS);
• make the assignment between the receiver modules and the device
channels (max 8 channels, each with a different priority: channel 1 = priority
1 = highest priority), so as to indicate to the MD3300MRP load manager
which receiver modules are to be piloted according to the priorities.
It is possible to assign more than one receiver module to each
channel in order to disconnect several loads at the same time. This
also allows simultaneous control of phase and neutral on the same
load, where this is deemed necessary.
If the absorbed power exceeds the set threshold continuously for the
pre-alarm time (Ton), the MD3300MRP load manager provides the loads
disconnection (receivers), starting from the lowest priority, as long as the
value of the absorbed power does not result lower than the activation
threshold. Once the alarm reset time (Toff) has elapsed, the device provides
the loads connection (receivers) in reverse order. The load manager and
the actuators communicate exclusively via radio.
RADIO RANGE
POWER Range:
• Inside 100 m² apartments with perpendicular crossing of main wall or
ceiling.
• 250m in open range.
Range may be reduced by presence of metallic elements, crossing of
walls or partitions.
2. INSTALLATION
Precautions for the installer
• The device must only be installed by qualified personnel in a closed
and adequately protected electrical panel, in accordance with national
installation standards.
• Before performing the installation operations, check that the devices
and conductors are not live.
• In order to comply with the safety regulations, the device must be connected
to an electrical line protected upstream by a magnetothermic switch (curve
C) with a current suitable for the load.
• Do not power on or connect the device if any part of it is
• After installation, inaccessibility to the connection terminals without
appropriate tools must be guaranted.
• The device can be used in environments with category of measurement
III and pollution degree 2.
For proper operation, the MD3300MRP load manager must measure the
same current as the general energy meter. For this reason the ideal position
for the device connection is immediately downstream of the general switch.
3. WIRING
Wiring via MTR2000ERP(X)
230V
L
50Hz
N
5454801
DS1054-074B
EN
damaged.
Two-pole
thermo-magnetic
circuit breaker
5454462
Wiring via MTR2000MRP(X)
230V
L
50Hz
N
5454801
Wires with cross-section area of 0.5 mm
IEC 60332-1-2; wires with cross section area smaller than 0.5 mm
comply with IEC 60332-2-2.
It is necessary to wire and power the MTR2000ERP(X) or MTR2000MRP(X)
receiver before the assignment with the MD3300MRP load manager.
Always make sure that the MTR module is configured with the default
values.
The MTR used for load control must manage electrical sockets. In this case, in
rest conditions, the MD3300MRP load control device periodically carries out
an automatic check of all the MTR modules, in order to restart them in a time
that can vary between 5 minutes and 40 minutes ".
4.
FIRMWARE RELEASE
Press and hold the keys
and
firmware release of the device.
5. RESET TO FACTORY SETTINGS
If you want to delete all the settings made and restore the factory values, press
the keys
and
simultaneously for more than 3 seconds. The display will
show "RESET". Factory values:
- Setpoint: 3.3 kW
- Ton: 60 seconds
- Toff: 120 seconds
CAUTION!: Resetting to the factory settings does not delete the radio
assignments made on the MD3300MRP device. To delete radio assignments,
see in detail chapter "REMOVING ALL RADIO ASSIGNMENTS".
6. TECHNICAL SPECIFICATIONS
Power supply: 230V~ (+10% -15%) - 50 Hz
Maximum own consumption: 4 VA
Direct current connection until 32A
Settable power threshold range: 0.8 ÷ 7 kW
Pre-alarm time range Ton: 10 ÷ 9999 seconds
Disconnection time range Toff: 10 ÷ 9999 seconds
Blocks for cables with maximum section of 6 mm
Radio frequency band: 2400 - 2480 MHz
Maximum radio power transmitted: 10mW
Operating temperature: -10°C ÷ +45°C
Operating humidity: 10% ÷ 90% non condensing
Storage temperature: -10°C ÷ +65°C
Container: 2 DIN modules
Overvoltage category: II
Operating altitude: below 2000 m (from 0 to 6560 ft)
Protection degree: IP20 / IP40 (on the front panel)
Indoor usage only, non-wet location
Insulation: reinforced between accessible parts (front panel) and all other terminals
Dimensions (H x L x D): 87,5 x 35,6 x 65 mm
7. KEY TO SYMBOLS
Symbol
~
Alternating input voltage
See the installation manual of the device
8. SIMPLIFIED EU DECLARATION OF CONFORMITY
Hereby, FDI Matelec SA., declares that the radio equipment type:
MD3300MRP load manager (code 5454801) is in compliance with Directive
2014/53/EU. The full text of the EU declaration of conformity is available at the
following internet address: www.Yokis.com
Directive 2012/19/EU of the European Parliament and of the Council of 4 July 2012
on waste electrical and electronic equipment (WEEE)
The symbol of the crossed-out wheeled bin on the product or on its packaging indicates that
this product must not be disposed of with your other household waste. Instead, it is your
responsibility to dispose of your waste equipment by handing it over to a designated collection
point for the recycling of waste electrical and electronic equipment. The separate collection and recycling
of your waste equipment at the time of disposal will help to conserve natural resources and ensure that
it is recycled in a manner that protects human health and the environment. For more information about
where you can drop off your waste equipment for recycling, please contact your local city office, your
household waste disposal service or the shop where you purchased the product.
Two-pole
thermo-magnetic
circuit breaker
5454464
or larger must comply with
2
for more than 3 seconds to display the
>3 seconds
2
Description
must
2

Advertisement

loading

Summary of Contents for Yokis MD3300MRP

  • Page 1 (max 8 channels, each with a different priority: channel 1 = priority that can vary between 5 minutes and 40 minutes “. 1 = highest priority), so as to indicate to the MD3300MRP load manager which receiver modules are to be piloted according to the priorities.
  • Page 2 The scanning operation allows the MD3300MRP device to be detected by For correct operation, it is essential to configure a radio assignment between the Yokis Pro App in order to subsequently carry out the assignment to the the MD3300MRP load manager and the MTR2000ERP(X) or MTR2000MRP(X) channels and the parameter configuration (Paragraphs 10 and 11) directly radio receiver relays.
  • Page 3 “Radio assignment between an MTR receiver module and the MD3300MRP load manager”. The MD3300MRP device is able to manage up to 8 channels, each with a different priority: channel 1 = priority 1 = highest priority.
  • Page 4 Setpoint parameter value will start flashing. MADE IN FRANCE Urmet S.p.a. – 10154 TORINO (ITALY) – Via Bologna 188/C - For technical information, go to www.yokis.com or call: Customer Service: +39 011.23.39.810 - export dept. Phone: +39 011.24.00.250/256...