15
Analog Parameters
Use the number keys to select the analog output number to edit and press the ENTER key. The
eight available analog output channels are referenced as analog output #1 to analog output #8.
The analog output #1 assignment is shown. To change this assignment press the MODE key.
Enter the tank number that analog output #1 will be assigned to, or enter "0" to disable the ana-
log output.
The default output value for analog output #1 is shown. This control parameter defines the state
of the analog output channel when system errors occur. System errors include uninitialized data
(after power-up), invalid volume data and tank gauge errors. Press the MODE key to change the
default output value. The available choices are 4 ma, 20 ma and LAST VAL.
The analog output #1 is assigned to TANK #1, PRODUCT. Press the MODE key to change the
analog control parameter. Available parameters are:
52
S E L E C T A N A L O G O U T P U T
T O E D I T :
' E n t e r ' T O C O N T I N U E
A N A L O G O U T P U T # 1
A S S I G N E D T O T A N K # 1
' M o d e ' T O C H A N G E
' E n t e r ' T O C O N T I N U E
A S S I G N O U T P U T # 1
T O T A N K # - -
E N T E R T A N K N U M B E R O R
' 0 ' T O D I S A B L E O U T P U T
A N A L O G O U T P U T # 1
O N S Y S E R R = 4 m a
' M o d e ' T O C H A N G E
' E n t e r ' T O C O N T I N U E
• Interface level
• GOVP
• Product level
• GOVI
• Temperature
• GOVT
( 1 - 8 )
• NSVP
• MASS
• GOVU