Handling Explanation - Daiichi Electronics FWVTT2-92A-33 Instruction Manual

Power flow three phase reactive power transducer
Table of Contents

Advertisement

6. Handling explanation

Please handle it correctly after paying attention to the following points.
(1) When applying the auxiliary power supply and input, check that the voltage and input signal of the
auxiliary power supply conform to the specifications of this product.
(2)Make sure that the external wiring is connected to the specified terminal position (listed on the
nameplate).
(3)Please use the output load within the output load range indicated on the name plate.
If the output load range is exceeded, not only will the output error, but the product will be
burdened. Especially for voltage output products, do not short-circuit the output.
This product will not be damaged even if the output terminal is left open in the current output
specifications. However, a voltage of about 15V is generated.
(4)The output adjustment range is BIAS:±5% of the output span, MAX.:±5% of the output span.
Use only when adjustment is required for matching with connected devices.
(5)The output value near 0 power factor switches between the power receiving side and the power
transmitting side within the range of LAG 90° or LEAD 90° ±3° (at rated current).
(Indefinite)
(6)The output value when only the auxiliary power supply is applied or when the auxiliary power supply
and voltage input are applied is the output equivalent to the received input 0kvar.