Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be performed by a qualified electrician. This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and hazards involved. For continued protection against shock hazard replace all covers and guards after field wiring is completed.
Risk of Fire and Electric Shock- Before installing or performing any service, the power MUST be turned OFF. All installations should be in compliance with the National Electric Code and all state local codes.
Risk of Burn- Disconnect power and allow product to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care.
Failure to comply with these instructions may result in death, serious bodily injury and property damage.
DISCLAIMER OF LIABILITY: Cooper LIghting Solutions assumes no liability for damages or losses of any kind that may arise from the improper, careless, or negligent installation, handling or use of this product.
Read carefully before installing product. Retain for future reference.
NOTICE: Product may become damaged and/or unstable if not installed properly.
Note: Specifications and dimensions subject to change without notice.
ATTENTION Receiving Department: Note actual product description of any shortage or noticeable damage on delivery receipt. File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All damaged material, complete with original packing must be retained.
NOTICE: Designed for indoor installation and use only.
Please refer to www.cooperlighting.com for our terms and conditions.
FCC Statement
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
FCC Part 15 Clause 15.21 Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
FCC Part 15.19a This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
FCC 2.1093/RSS-102 This product complies with the RF exposure limit set forth for an uncontrolled environment and are safe for intended operation as described in this manual.
ISED RSS This device complies with Industry Canada's licence-exempt RSSs. Operation is subject to the following two conditions:
The Wireless Wallstation is an integral part of the WaveLinx Wireless system and is available in three button configurations in white color. These Wallstations are line voltage (120-277VAC) powered and are fully configurable to provide wireless local and multi-level control of the lighting in an area. The Wallstations operate on a Bluetooth Mesh network.
The Wallstation mounts in a standard wallbox (single or multi-gang) and is suitable for standard wall plates (not included). Each button is pre-configured to control an area and each button's to control a lighting scene for an area and each button's functionality can be modified using the WaveLinx Wireless Mobile Application.
The Wallstation is a multi-scene, single area dimming Wallstation which provides customized light level for each area.
The Wallstation provides default sequence of operations including 50% light level, scene light levels between 30-70% as well as 100% and full off. Two configurations also include raise/ lower buttons to allow further light level manual adjustment.
Notes:
Designed for installation into a standard single or multi- gang wiring box, each wallstation is installed in the same manner as an ordinary wall switch.
Note: Before installing the unit in the junction box, please wire the wall station per the instructions listed in the "Wiring Diagram" section.
Wall plate not included
Technology: Wireless Wallstation for Lighting and Scene control utilizing Bluetooth Mesh.
Power | Input power:
|
Indicators | White LED (1 per wallstation) LED functionality
|
Button Configurations |
|
Installation | Standard gang decorator opening (wall plate not included) |
Wallstation Size | 4.2"H x 1.8"W x 1.5" D (1.3" in box) 107mm x 45mm x 36mm (32mm in box) |
Environmental Specifications | Operating Temperature Range: 32°F to 113°F (0°C to 45°C) Storage Temperature Range: 32°F to 167°F ( 0°C to 75°C) Relative Humidity: 5% to 95% non-condensing, for indoor use only |
Standards | Listings: cULus Certified, FCC Meets latest ASHRAE Standard 90.1 requirements Meets latest IECC requirements Meets latest CEC Title 24 requirements |
Wireless Specifications | Radio 2.4GHz IEEE 802.15.4 Transmitter Power +7dBm Range: 100ft (30m) LOS (see Note) 150 devices per Wireless Area Controller (100 best practice) |
Note: Use of a metal wall plate will result in reduced wireless range.
The WaveLinx Wireless Wallstation is intended to fit into a standard wall box with a minimum internal depth of 2 inches (51 mm).
Button 1 | Scene 3 = 50% |
Button 2 | Scene 1 = 100% |
Button 3 | Scene 2 = 70% |
Button 4 | Scene 4 = 30% |
Raise press* hold* | Increase 1% (per press) Increase 15% (per sec) |
Lower press* hold* | Decrease 1% (per press) Decrease 15% (per sec) |
Power* | Scene 0 = OFF |
* - affects all zones in area
Note: Please refer to the WaveLinx Wireless Mobile Application User Manual for complete configuration information.
There are two major LED patterns for a Wallstation:
Issue | Possible Causes | Suggestions |
LED will not blink when button is pressed | Power Interrruption | Check incoming voltage and/or wiring |
LED blinks for 10 seconds after button press | No network connection | Check that the wallstation connected to the WaveLinx Wireless network. |
Wallstation cannot connect to the WaveLinx Wireless network | Communication Issue | Check that the Wallstation is within range of other WaveLinx Wireless devices in the same network without obstacles and can establish reliable communicatins. |
Button toggles incorrect scene | Configuration Issue | Check that the wallstation button was programmed with the correct scene via the WaveLinx Wireless mobile application. |
If still having trouble, call Technical Services at 1-800-553-3879
Cooper LIghting Solutions is a registered trademark.
All trademarks are property of their respective owners
Product availability, specifications, and compliances are subject to change without notice.
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
www.cooperlighting.com
For service or technical assistance: 1-800-553-3879
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2020 Cooper Lighting Solutions
All Rights Reserved
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Cooper WaveLinx Wireless Wallstation Installation Instructions
Advertisement
Need help?
Do you have a question about the WaveLinx Wireless Wallstation and is the answer not in the manual?
Questions and answers