The setpoint of the room temperature is determined outside temperature-dependent by means of a control curve with 8 points.
Example:
Outdoor temperature [°C]
-20
-15
-10
-5
0
5
10
15
Control function
Mode
Outd comp room
If cascade control
Max/min supply setp
Max: XX.X °C
Min: XX.X °C
Outdoor comp setp
-20.0 °C = 25.0 °C
-15.0 °C = 24.0 °C
-10.0 °C = 23.0 °C
Outdoor comp setp
-5.0 °C = 23.0 °C
0.0 °C = 22.0 °C
.0 °C = 20.0 °C
Outdoor comp setp
10.0 °C = 18.0 °C
15.0 °C = 18.0 °C
Room Temperature [°C]
18
18
20
22
23
23
24
25
->