TROUBLESHOOTING DF2500 DIRECT FIRED HEATER
PROBLEM
Heater overheating
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
pg. 14
3. Gas Burner ports obstructed.
4. Air proving switch defective.
5. Flame rod dirty – defective.
6. Inadequate fuel delivery.
CONDITION
1. Gas pressure excessive.
2.
RTC
Discharge
Temperature Sensor
defective.
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
3. Clean – replace burner.
4. Replace Air Proving Sw.
5. Clean, Replace Flame Rod.
6. Fill Tank – replace regulators,
valves – check gas lines for
obstructions.
REMEDY
1. Adjust – replace regulator.
2.
Replace
troubleshoot modulation
system.