2.4 Cooling and Heating Data Sheet in Rated Frequency

Cooling:
Rated cooling
condition(°F) (DB/WB)
Outdoor
Indoor
80/66.9
95/-
80/66.9
95/-
80/66.9
95/-
Heating:
Rated heating
condition(°F) (DB/WB)
Outdoor
Indoor
70/60
19.94/19.04
70/60
19.94/19.04
70/60
19.94/19.04
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6ft.
10
Pressure of gas pipe
connecting indoor and
Model
outdoor unit
P (PSIG)
12K
123.2~145
18K
130~142
24K
130~142
Pressure of gas pipe
connecting indoor and
Model
outdoor unit
P (PSIG)
12K
362.3~435
18K
507~550
24K
507~550
Inlet and outlet pipe
temperature of heat
exchanger
T1 (°F)
T2 (°F)
in:46~52
in:122~176
out:52~57
out:99~109
in:46.4~51.8
in:167~181.4
out:51.8~57.2
out:98.6~118.4
in:46.4~51.8
in:167~181.4
out:51.8~57.2
out:98.6~118.4
Inlet and outlet pipe
temperature of heat
exchanger
T1 (°F)
T2 (°F)
in:122~176
in:34~37
out:99~109
out:36~41
in:167~181.4
in:33.8~37.4
out:98.6~113
out:35.6~42.8
in:167~181.4
in:33.8~37.4
out:98.6~113
out:35.6~42.8
Fan speed of
Fan speed of
indoor unit
outdoor unit
Suprt High
High
Super High
High
Super High
High
Fan speed of
Fan speed of
indoor unit
outdoor unit
Super High
High
Super High
High
Super High
High
Technical Information
Service Manual
Compressor
revolution
(rps)
58
73
75
Compressor
revolution
(rps)
56
75
80