Capacity Variation Ratio According To Temperature; Cooling And Heating Data Sheet In Rated Frequency - Lennox LM036CI-100P232-1X Service Manual

Hide thumbs Also See for LM036CI-100P232-1X:
Table of Contents

Advertisement

2.2 Capacity Variation Ratio According to Temperature

Cooling:
105
100
95
90
85
80
75
70
65
60
55
50
32
33
34
35

2.3 Cooling and Heating Data Sheet in Rated Frequency

Cooling:
Rated cooling
condition(°C)
(DB/WB)
Indoor
Outdoor
27/19
35/24
Heating:
Rated heating
condition(°C)
(DB/WB)
Indoor
Outdoor
20/15
7/6
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
6
Conditions
Indoor:DB27°C/WB19°C
Indoor air flow:Super High
Pipe length:5m
36
37
38
39
40
41
Outdoor temp.(°C)
Model
All models
Model
All models
Heating:
120
100
80
60
40
20
0
42
43
-7
Pressure of gas pipe
connecting indoor and
outdoor unit
P (MPa)
T1 (°C)
0.48 ~ 0.7
7.2 to 9.6
Pressure of gas pipe
connecting indoor and
outdoor unit
P (MPa)
T1 (°C)
1.85 ~ 2.05
78.4 to 38
Conditions
Indoor:DB20°C/WB15°C
Indoor air flow:Super High
Pipe length:5m
-5
0
Outdoor temp. (°C)
Inlet and outlet pipe
temperature of heat
Fan speed of
exchanger
indoor unit
T2 (°C)
78.1 to 38.5
Supper High
Inlet and outlet pipe
temperature of heat
Fan speed of
exchanger
indoor unit
T2 (°C)
-0.9 to 16
Supper High
Service Manual
5
7
10
Fan speed
of outdoor
unit
High
Fan speed
of outdoor
unit
High
Technical Information

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lm036co-100p232-1xLm036hi-100p232-1xLm036ho-100p232-1x