3. Unit Placement and Clearances
1. Outdoor units should be located in an area protected from prevailing winds. (shown below)
In high wind locations it may be advisable to locate the units within a walled area.
Prevailing wind
2. If the units are surrounded by an enclosure, the discharge of the air damper must direct the air out and over the
enclosure walls to prevent air recirculation.
Top View
Building Wall
Outdoor Unit
Installation Method
H ≤ discharge
of air damper
Installation manual 15