QUICK START GUIDE
Information: Controller Basic Operation
View and change system parameters from the factory defaults via
A) Controller Display
B) Craft Port on front of controller using a laptop with EasyView2 software or HyperTerminal.
Easy View2 (GUI) software can be downloaded from
C) J5 LAN port web pages using a laptop with browser. LAN port Server mode is for local laptop connection. Set the LAN
port to Server:
With the controller set to Server enter the default IP address 192.168.2.1 (default) in the web browser address field.
Warning: Do not connect J5 LAN port to a network when set to Server. Set the controller to Client or Static before
connecting to the network. Static is the factory default setting and the typical setting for most networks.
Controller Alarm Status: The display changes colors; Green = Normal, Amber = Minor Alarm, Red = Critical/Major
Alarm
Some alarms may occur during initial installation; example: thermal probe fail or Major/Minor communication fail .
Clear these alarms: Via Controller Display: follow the menu path; Menu > Control/Operation > Clear Events or
Uninstall Equipment.
Via web pages or EasyView2; Select the Maintenance tab > clear latched events and clear missing devices.
Verify Basic Installation Settings: Date, Time, Battery Type, number of strings and float voltage
Controller Display - Menu > Configuration > System Settings and Menu > Configuration > Batteries.
Web pages or EasyView2 - Installation Tab for Date, Time. Site ID and Site Description.
Settings Tab > Battery Management for Battery Type and number of battery strings installed.
Plant Status LEDs
Craft Port
behind door
LCD Display
Voltage
Test Jacks
Front Display
Page 7
© 2021 ABB. All rights reserved.
Menu
Navigation
abbpowerconversion.com
Front Display Menu Map